7. Remote monitoring panel (option)
The remote monitoring panel (Figure 61) enables you to monitor the UPS from a distance. It can be located
a maximum distance of 50 m from the UPS. The remote monitoring is connected directly to the UPS with a
4-wire cable via the D9-type Alarm connector on the rear of the controller (Figure 62). It shows you the
current status of the LEDs on the UPS.
The remote monitoring panel has only one button – the "Alarm Off" button, which enables you to
temporarily silence the audible alarm.
LED
BYPASS
B/P
OVERLOAD
BATTERY
CHARGER
INVERTER
INV
LOAD LEVEL
UPS ON
ALARM OFF
Centric 3x480 Vac, Installation Guide, rel. 2.2
G
AMATRONIC
Figure 61: The remote monitoring panel
Table 13: LEDs on the remote monitoring panel
C
INDICATOR
OLOR
green
red
red
red
red
green
green
red
green
red
green
green
red
green
red
E
I
L
LECTRONIC
NDUSTRIES
M
EANING
Bypass input is normal
Bypass fault
The load is on the bypass voltage
Overload, load moved to bypass
Battery fault
Battery normal
Input voltage is OK
Input voltage not OK
Inverter is operating normally
Inverter is faulty
The load is on the inverter
Load level normal
Excessive load
UPS is operating
The audible alarm has been muted
.
TD
59