Status (1-2-4)

Select Configure / Setup, Detailed Setup, and Status.
Follow the prompts on the Field Communicator display
to configure the following parameters: Instrument
Time, Calibration and Diagnostics, Operational, and

Integrator.

D Instrument Time (1-2-4-1)
D Inst Time Invalid Enab—Yes or No. When
enabled indicates if the Instrument Time Invalid
alert is active. Factory default is Yes.
D Inst Date and Time—Permits setting the
instrument clock. When alerts are stored in the
alert record, the record includes the time and date.
The instrument clock uses a 24-hour format.
D Calibration & Diagnostics (1-2-4-2)
D Cal in Progress Enab—Yes or No. When
enabled indicates that calibration is in progress.
Factory default is No.
D AutoCal in Progress Enab—Yes or No. When
enabled indicates that auto calibration is in
progress. Factory default is No.
D Diag in Progress Enab—Yes or No. When
enabled indicates that a diagnostic test is in
progress. Factory default is No.
D Diag Data Avail Enab—Yes or No. When
enabled indicates when there is diagnostic data
available. Factory default is Yes.
D Operational (1-2-4-3)
D Press Cntrl Active Enab—Yes or No. When
enabled indicates when Pressure Control is active.
Factory default is Yes.
D Multi-Drop Enab—Yes or No. When enabled
indicates the digital valve controller is operating in a
multi-drop loop. Factory default is No.
D Integrator (1-2-4-4)
D Integrator Sat Hi Enab—Yes or No. When
enabled indicates when the Integrator Saturated
High alert is active. Factory default is Yes.
D Integrator Sat Lo Enab—Yes or No. When
enabled indicates when the Integrator Saturated Lo
alert is active. Factory default is Yes.
September 2010
Detailed Setup
TRAVEL
RANGE
HIGH
ZPC = OPEN
ZPC = CLOSED
THE SHAPE OF
THESE LINES DEPENDS ON
THE INPUT CHARACTERISTICS
TRAVEL
LINEAR CHARACTERISTIC SHOWN
RANGE
LOW
ANALOG INPUT
INPUT RANGE
mA OR % OF 4-20 mA
LOW
NOTE:
ZPC = ZERO POWER CONDITION
A6531-1 / IL
Figure 4-5. Calibrated Travel to Analog Input Relationship
D Integ Limit—The Integral Limit provides an
upper limit to the integrator output. The high limit is
configurable from 0 to 100% of the I/P drive signal.
D Integ DeadZ—Integral Dead Zone is a window
around the Primary Setpoint in which integral
action is disabled. This feature is used to eliminate
friction induced limit cycles around the Primary
Setpoint when the integrator is active. The Dead
Zone is configurable from 0% to 2%, corresponding
to a symmetric window from 0% to +/−2% around
the Primary Setpoint. Default value is 0.25%.

Instrument (1-2-5)

Select Configure / Setup, Detailed Setup, and
Instrument. Follow the prompts on the Field
Communicator display to configure the following
Instrument parameters: General, Units, Analog Input
Range, Relay Type, Zero Pwr Condition (Zero Power
Condition), Max Supply Press (Maximum Supply
Pressure), Aux Term Mode (Auxiliary Terminal Mode)
Inst Date and Time (Instrument Date and Time), and
Calib Status and Loc (Calibration Status and
Location).
D General (1-2-5-1)
D HART Tag—Enter an up to 8 character HART
tag for the instrument. The HART tag is the easiest
way to distinguish between instruments in a
multi-instrument environment. Use the HART tag to
label instruments electronically according to the
requirements of your application. The tag you
4
INPUT RANGE
HIGH
47