Single-Acting Relays; Restore Factory Settings - Fisher FIELDVUE DVC6200 Instruction Manual

Digital valve controller
Hide thumbs Also See for FIELDVUE DVC6200:
Table of Contents

Advertisement

ADJUSTMENT DISC

Single-Acting Relays

WARNING
For Instrument Level ODV only:
If the unused port is monitoring
pressure, ensure that the pressure
source conforms to ISA Standard
7.0.01 and does not exceed the
pressure supplied to the instrument.
Failure to do so could result in
personal injury or property damage
caused by loss of process control.
Single-Acting Direct Relay
The single-acting direct relay is designated by "Relay
C" on a label affixed to the relay itself. Relay C
requires no adjustment.
Single-Acting Reverse Relay
The single-acting reverse relay is designated by
"Relay B" on a label affixed to the relay itself. Relay B
is calibrated at the factory and requires no further
adjustment.
September 2010
W9034
Figure 5-1. Relay A Adjustment (Shroud Removed for Clarity)
FOR SINGLE-ACTING DIRECT RELAYS:
ROTATE ADJUSTMENT DISC IN THIS
DIRECTION UNTIL IT CONTACTS THE
BEAM
FOR DOUBLE-ACTING RELAYS:
ROTATE ADJUSTMENT DISC IN
THIS DIRECTION TO DECREASE
OUTPUT PRESSURE
FOR DOUBLE-ACTING RELAYS:
ROTATE ADJUSTMENT DISC IN
THIS DIRECTION TO INCREASE
OUTPUT PRESSURE
Restoring Factory Settings (1-3-4)
Note
After restoring factory settings you will
need to re-configure and calibrate the
instrument.
From the Online menu, select Configure / Setup, then
select Calibrate, and Restore Factory Settings. Follow
the prompts on the Field Communicator display to
restore calibration and all parameters to the factory
settings. You should only restore the calibration if it is
not possible to calibrate an individual sensor.
Restoring calibration returns the calibration of all of the
sensors and the tuning set to their factory settings.
Following restoration of the factory calibration, the
individual sensors should be recalibrated.
Calibration
5
59