Fisher FIELDVUE DVC6200 Instruction Manual page 13

Digital valve controller
Hide thumbs Also See for FIELDVUE DVC6200:
Table of Contents

Advertisement

Available Mounting
J
Integral mounting to the Fisher GX Control
Valve and Actuator System
J
Integral mounting to Fisher rotary actuators
J
Sliding-stem linear applications
J
Quarter-turn rotary applications
DVC6200 digital valve controllers can also be
mounted on other actuators that comply with
IEC 60534-6-1, IEC 60534-6-2, VDI/VDE 3845 and
NAMUR mounting standards.
Input Signal
Point-to-Point:.
Analog Input Signal: 4−20 mA DC, nominal; split
ranging available
Minimum Voltage Available at Instrument Terminals
must be 10.5 VDC for analog control, 11 VDC for
HART communication
Minimum Control Current: 4.0 mA
Minimum Current w/o Microprocessor
Restart: 3.5 mA
Maximum Voltage: 30 VDC
Overcurrent protected
Reverse Polarity protected
Multi-drop:.
Instrument Power: 11 to 30 VDC at 8 mA
Reverse Polarity protected
Output Signal
Pneumatic signal, up to 95% of supply pressure
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig)
Action: J Double, J Single Direct or J Reverse
(1)
Supply Pressure
Minimum Recommended: 0.3 bar (5 psig) higher
than maximum actuator requirements
Maximum: 10.0 bar (145 psig) or maximum
pressure rating of the actuator, whichever is lower
Medium: Air or natural gas
Air: Supply pressure must be clean, dry air that
meets the requirements of ISA Standard 7.0.01. A
maximum 40 micrometer particle size in the air
system is acceptable. Further filtration down to 5
micrometer particle size is recommended. Lubricant
content is not to exceed 1 ppm weight (w/w) or
volume (v/v) basis. Condensation in the air supply
should be minimized
Natural Gas: Natural gas must be clean, dry,
oil-free, and noncorrosive. H
exceed 20 ppm.
September 2010
Introduction and Specifications
Table 1-2. Specifications
S content should not
2
−continued−
Steady-State Air Consumption
Standard Relay:
At 1.4 bar (20 psig) supply pressure: Less than 0.38
3
normal m
/hr (14 scfh)
At 5.5 bar (80 psig) supply pressure: Less than 1.3
3
normal m
/hr (49 scfh)
Low Bleed Relay:
At 1.4 bar (20 psig) supply pressure: Average value
3
0.056 normal m
/hr (2.1 scfh)
At 5.5 bar (80 psig) supply pressure: Average value
3
0.184 normal m
/hr (6.9 scfh)
Maximum Output Capacity
At 1.4 bar (20 psig) supply pressure: 10.0 normal
3
m
/hr (375 scfh)
At 5.5 bar (80 psig) supply pressure: 29.5 normal
3
m
/hr (1100 scfh)
Operating Ambient Temperature Limits
−40 to 80_C (−40 to 176_F)
−52 to 80_C (−62 to 176_F) for instruments utilizing
the Extreme Temperature option (fluorosilicone
elastomers)
Independent Linearity
Typical Value: ±0.50% of output span
Electromagnetic Compatibility
Meets EN 61326-1 (First Edition)
Immunity—Industrial locations per Table 2 of
the EN 61326-1 standard. Performance is
shown in table 1-3 below.
Emissions—Class A
ISM equipment rating: Group 1, Class A
Lightning and Surge Protection—The degree of
immunity to lightning is specified as Surge immunity
in table 1-3. For additional surge protection
commercially available transient protection devices
can be used.
Vibration Testing Method
Tested per ANSI/ISA-S75.13.01 Section 5.3.5. A
resonant frequency search is performed on all three
axes. The instrument is subjected to the ISA
specified 1/2 hour endurance test at each major
resonance.
(2,3)
(2,3)
(1)
5
1