DSC 3G4010 Installation Manual page 21

3g hspa cellular alarm communicator
Hide thumbs Also See for 3G4010:
Table of Contents

Advertisement

The following wiring diagrams (Figures 6 to 8) are examples of ULC Listed Fire Monitoring Installation connections.
3G4010 Wiring Diagrams
Figure 6: Wiring Diagram for Fire Alarm Control Unit (with dialler) and 3G (HSPA/2G (GPRS) Transmitter
NOTES:
Power for 3G4010 shall be provided from Fire Alarm Control Unit or separately listed power supply rated for the applic-
l
ation, 12V/700mA.
All wiring connections must be run in a protective conduit.
l
For local supervision of the wireless transmitter connect PGM output from 3G4010 to one zone input on the Fire Alarm Con-
l
trol Unit.
Dry Contact Trouble output from ULC Listed Fire Alarm Control Unit must be connected to zone input on the 3G4010 for
l
supervision of Tip/Ring connection.
Fire Alarms must be sent over both communication channels. Fire output from Fire Alarm Control Unit must be connected
l
to the Input 1 on the 3G4010.
24h Test Transmission must be enabled on the dialler and on the 3G4010.
l
Figure 7: DSC Subscribers' Unit Fire and 3G Transmitter Mounted in the Same Room
DSC Keypad
LCD4501
PK55XX
Fire Alarm Control Unit
NOTES:
Power for 3G4010 must be provided from Fire Alarm Control Unit or separately listed power supply rated for the applic-
l
ation (12V/700mA).
All wiring connections must be run in a protective conduit.
l
Phone Line Monitoring (TLM) must be enabled.
l
Phone Line trouble is indicated by Blue LED on 3G4010.
l
Connect PGM4 output from 3G4010 (Trouble Conditions) to a zone input on the Subscriber Unit for supervision of the
l
GSM Transmitter.
24hr Test Transmission over phone line (PSTN) and 3G4010 must be enabled.
l
Fire Alarms must be sent over both communication channels.
l
On the Subscribers' Unit, program PGM1 for PC1616/PC1832/PC1864 as System Event (Section [009] as type 10; Sec-
l
tion [501] Fire Event option 2 ON). An alternate option is to program PGM1 as ZoneFollower (Sec [009] = 29) and assign
Fire Zone to PGM1in Section [551]. Ensure Bit 3 is on in [501]. In this case,a restored fire alarm condition does not require
the DSCcontrol panel to be reset.For PC4020 program PGM1 as type 49 Steady Fire ([00070049]).
Dry contact outputs from ULC Listed Fire Alarm Control Unit must be connected to zone inputs on the ULC Listed DSC Sub-
l
scribers' Unit Fire.
Refer to detailed diagrams in Figure 7.
l
(Passive Communication System)
AUX Power
Fire Alarm
(12V/700mA)
Control Unit
TIP/RING
Zone Input
Outputs
Fire
Trouble
AC Input
DSC
Subscribers'
Unit Fire
Outputs
Zone
Fire
Inputs
Supervisory
TIP
PC4020
Trouble
PC1864
PC1832
PC1616
AC Input
AC Input
3G Cellular
Transmitter
3G4010
T1/R1
TIP/RING
Zone
PGM4
Inputs
Output
RM1C ULC
Relay
3G4010 cabinet
AUX Power
3G Cellular
12V/700mA
Transmitter
3G4010
T1/R1
TIP
RING
Zone
Input
PGM1
RM1C ULC
Relay
RM1C ULC
Relay
PC5003C
PC4050CR
3G4010 cabinet
cabinet
21
3G (HSPA) or
2G (GPRS)
PSTN
3G (HSPA)/2G (GPRS)
TIP/RING
PSTN
PGM4