9 POSITIONER FUNCTIONS (No
Display Required)
The following features can be performed using the local
interface.
No display is required for these features.
Additional features are offered with the use of a display,
Handheld or DTM.
NOTE: In order to prevent unintentional adjustments of
the configuration, tuning, or control of the valve, the Tamper
Lock feature may be used.
disables the buttons and menus except for the ability to view
the status of the positioner. When locked, the positioner may
be temporarily unlocked by entering a PIN.
required to enter the PIN.)
unlocked from the DTM.
9.1
Live Manual Tuning (Adjusting the
Gain)
Use the Selectable GAIN Switch to adjust the gain at any
time
during
operation.
immediately. For faster response select settings above "E"
(F-J). For more stable response, select settings below "E"
(B-D). See Figure 16: Selectable GAIN Switch.
9.2

Local Control Of Valve Position

To manually adjust the position of the valve regardless of the
input command (analog or digital), press and hold the ▲Up,
▼Down and ◄ BACK buttons for about 3 seconds.
▲Up, ▼down buttons can then be used to position the valve.
While in this mode the LED's will flash a GRRY (green-red-
red-yellow) sequence. To exit the local control mode and
return
to
normal
operation,
ACCEPT/QUICK-CAL button.
WARNING: When operating using local control of the
valve, the valve will not respond to external commands.
Notify proper personnel that the valve will not respond to
remote command changes, and make sure the valve is
properly isolated.
9.3

Command Source Reset

Performing a command source reset will reset the command
source to analog if it has been inadvertently left in digital
mode. This is done by holding down both the ▲Up and
▼Down
buttons,
then
►ACCCEPT/QUICK-CAL button.
9.4

Factory Reset

To perform a factory reset, hold ► ACCEPT/QUICK-CAL
button while applying power.
including calibration will be reset to factory defaults. The
positioner must be re-calibrated after a factory reset. Tag
names and other user configured limits, alarm settings, and
valve information will also be lost and need to be restored. A
factory reset will always reset the command source to analog
4-20 mA.
NOTE: Once the Multi-Function Card (MFC) type has
been configured, the type selection will still remain after a
factory reset.
WARNING: Performing a factory reset may result in the
inability to operate the valve until reconfigured properly.
Notify proper personnel that the valve may stroke, and make
sure the valve is properly isolated.
© Flowserve Corporation
User Instructions - Logix® 520MD+ Series Digital Positioner
This is set in the DTM and
(An LCD is
Or, the positioner can be
This
adjustment
takes
briefly
press
the
briefly
pressing
All of the internal variables
9.5

Viewing Version Numbers

The version number of the embedded code may be checked
at any time except during a calibration. To see the major
version number, hold the ▲Up button. This will not alter the
operation of the unit other than to change the blink sequence
to 3 blinks indicating the major version number. Holding the
▼Down button will give the minor version number without
affecting operation. The version codes are interpreted by
adding up the numbers assigned according to the following
table:
Table 14: Viewing Version Numbers
First Blink
Color
Value
Green
Yellow
Red
For example, if holding the ▲Up button gave a G-G-R code,
and holding the ▼Down gave a Y-Y-G code then the
effect
resulting version number would be (0+0+2).(9+3+0) or
version 2.12.
The
the
23
Field Trial Version – Printed October 28, 2011
FCD LGENIM0105-00
Second Blink
Value
0
0
9
3
18
6
Third Blink
Value
0
1
2