226 Technical data

DC connection data

Voltage (U
)
2
6-pulse modules
Voltage (U
)
2
12-pulse modules
Power
systems

Efficiency

Control unit connection data

See chapter
Control unit
Degree of
protection
ACS880-304-xxxxA-3+A018: 513 ... 560 V DC. This is indicated in the type
designation label as typical output voltage level 540 V DC.
ACS880-304-xxxxA-5+A018: 513 ... 675 V DC. This is indicated in the type
designation label as typical output voltage levels 540/648/675 V DC.
ACS880-304-xxxxA-7+A018: 709 ... 932 V DC (709 ... 810 V DC for UL/CSA).
This is indicated in the type designation label as typical output voltage levels
709/810/932 V DC (810 V DC for UL/CSA).
ACS880-304-xxxxA-3+A018: 532 ... 581 V DC. This is indicated in the type
designation label as typical output voltage level 560 V DC.
ACS880-304-xxxxA-5+A018: 532 ... 700 V DC. This is indicated in the type
designation label as typical output voltage levels 560/672/700 V DC.
ACS880-304-xxxxA-7+A018: 735 ... 966 V DC (735 ... 840 V DC for UL/CSA).
This is indicated in the type designation label as typical output voltage levels
735/840/966 V DC (840 V DC for UL/CSA).
TN (grounded) and IT (ungrounded) systems)
> 98%
on page 231.
Module IP00, UL open type