174 Ordering information
Diode supply units – 3×D8T, 6-pulse
This section lists the component ordering codes for a diode supply unit which:
•
consists of three D8T supply modules
•
have a 6-pulse connection to AC power line
•
is installed in the Rittal TS 8 enclosure or in a generic cabinet.
In the Rittal installations, the supply unit consist of one 1×D8T supply module cubicle and
one 2×D8T supply module cubicle. In the generic cabinet installations, the supply unit
consist of one 3×D8T supply module cubicle.
Diode supply modules – 3×D8T, 6-pulse
The Type designations and power ratings for the modules are given in section
page 215. The type designation is the ordering code for the modules.
Diode supply module type
U
= 400 V
N
ACS880-304-2730A-3+A018
U
= 500 V
N
ACS880-304-2730A-5+A018
U
= 690 V
N
ACS880-304-2280A-7+A018
Ordering code format
[Module type] + code [+code] ...
For example,
ACS880-304-0910A-3 +A004+A018
Note: The following components are always required to construct a working unit out of the
modules and you must order them separately:
•
BCU control unit kits. See section
•
A pair of fiber optic cables for the communication link between the control unit and
each module. See section
•
Control circuit plug connectors for each supply module. See section
plug connectors for supply modules
•
Quick connectors (3AUA0000119227) for each module. See section
for D8T module
•
Varistor board (UL/CSA installations only). For more information, see
6- and 12-pulse
Frame
size
3xD8T
3xD8T
3xD8T
Control units
Fiber optic cables for supply modules
on page 188.
on page 213.
Contents
• diode supply modules with half-controlled diode-
thyristor bridges and speed-controlled cooling fans as
standard
Option codes
+C183: Internal heating element in the module
+C188: Direct-on-line (DOL) cooling fan (400 V)
+G304: 115 V auxiliary voltage supply
Note: D8T DOL fan is always 400 V.
on page
on page 188.
Ratings
186
.
on page 187.
Control circuit
Quick connector
Varistor board –
on