Incoming cubicle

We recommend a separate incoming cubicle beside the supply module cubicle for the
main AC fuses and switching and disconnecting devices. There is an example in section
Layout drawing of the supply unit

Example of the AC fuse cooling

The AC fuses must be cooled by forced cooling. If the fuses are not located in the same
cubicle with the rectifier module, the module cooling fan does not supply the cooling air for
the fuses but you must use a separate cooling fan. The following figures show an example
of the cooling system using a thermal switch for the air temperature monitoring near the
AC fuses.