112 Installation checklist
Check that...
The ambient operating conditions meet the specifications given in chapter
Technical
data.
The cabinet has been fixed to floor, and if necessary due to vibration etc, also from top to the wall or
roof.
The cooling air flows freely, and air recirculation inside the cabinet is not possible.
There is sufficient free space around the drive cabinet. See section
Construction of supply module
cubicle – 2×D7T, 12-pulse, Rittal TS 8
on page 51.
There is an adequately sized protective earth (ground, PE) conductor between the drive and the
switchboard.
The conductor has been connected to appropriate terminal.
Connection of the PE conductor is tight: Pull the conductors to check.
Proper grounding has been measured according to the local regulations.
The enclosures of the equipment in the cabinet have proper galvanic connection to the cabinet
protective earth (ground) busbar; The connection surfaces at the fastening points are bare
(unpainted) and the connections are tight, or separate grounding conductors have been installed and
the connections are tight (pull the conductors to check).
The main circuit connections inside the drive cabinet correspond to the circuit diagrams.
The supply voltage matches the nominal input voltage of the unit. Check the type designation label.
The input power cable has been connected to the appropriate terminals, the phase order is right, and
the terminals have been tightened. (Pull the conductors to check.)
Appropriate AC fuses and main disconnector have been installed.
The control cables (if any) have been connected to the appropriate terminals, and the terminals have
been tightened. (Pull the conductors to check.)
There are no tools, foreign objects or dust from drilling inside the cabinet.
The installation of the inverter modules and motor cable has been checked. See ACS880-104
inverter modules Hardware manual (3AUA0000104271 [English]).
All shrouds and covers are in place. Cabinet doors have been closed.