Status
Phase loss fault
Red Fault LED steady lighting, and LCD
1
event code EF1x
.
See chapter 6.1.2.1 about LED status indi-
cators activation for faults and protections.
Ready
Run
Protection
Bad network quality
Red Fault LED steady lighting, and LCD
event code EF20.
See chapter 6.1.2.1 about LED status indi-
cators activation for faults and protections.
Ready
Run
Protection
Current lost fault
Red Fault LED steady lighting, and LCD
1
event code EF3x
.
See chapter 6.1.2.1 about LED status indi-
cators activation for faults and protections.
Ready
Run
Protection
SF = Softstarter fault
EF = External fault
P = Protection
x = phase number, 4 indicates multiple or unknown phase
1
90
Chapter 10
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
Possible cause
Fuse blown.
Power loss on operational current on one
or several phases.
Fault
The main contactor or circuit breaker is
open.
Main contactor opens too quickly at stop.
Excessive disturbances in the operational
supplying network.
Short power loss on all three phases in the
Fault
operational network.
Operational current too low or lost on one
or several phases.
Fault
Phase loss on line side or motor side.
Thyristors not able to conduct
The motor is too small.
(current is out of measuring range).
Solution
Check and replace fuses in all three
phases.
Check and correct supplying opera-
tional network.
Check and close contactor/breaker or
any external switching device.
Control main contactor with Run
signal relay on terminal 4. See chapter
5.2.4.6.
Add a time relay before contactor
opening.
If Stop Ramp not is needed, set Stop
Ramp Time to 0.
Check and correct supplying opera-
tional network.
Check and correct supplying opera-
tional network.
Check and correct supplying network
Check and correct supplying network
See Phase loss EF14.
Check and replace PCB/thyristor.
Contact your ABB Sales Office for
replacement kit.
Check that the softstarter corresponds
to the motor size.