Quickstart - ABB PSE 18 Installation And Commissioning Manual

Hide thumbs Also See for PSE 18:
Table of Contents

Advertisement

A
Ready
Run
Protection
Exit
C
E
Figure 2.1:
A
LED status indicators.
B
LCD display with backlight.
C
Exit key for cancelling parameter edits and
moving up one menu level.
D
Select/Reset key for changing and storing
parameter values, moving down one menu
level, and to reset tripping events.
E
Navigation keys for navigating the menu and
changing parameter values. Flashing numbers
or text shown in the display indicates that the
menu/value can be changed or scrolled.
L1
L2
L3
N
L N
KM1
1L1 3L2 5L3
1 2
2T1 4T2 6T3
U
V
W
M
3
Figure 2.2: Example connection of PSE Softstarter
12
Chapter 2
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
B
Fault
Select
Reset
D
Start
Stop
8
9
11
Start
Stop
8
9
10
11
12
13
14
Run TOR
Fault
NC
NO
3
4
5
6
7
Chapter 2 Quickstart
This chapter is a short guide on how to connect, configure and start the
softstarter in the easiest way.
This product has been carefully manufactured and tested but there is a
risk that damage can occur from abnormal handling during transportation.
Therefore, the procedure below should be followed during initial installation:
Warning!
Mounting, electrical connection and settings of the softstarter shall
be made in accordance with existing laws and regulations and be
performed by authorized personnel.
Warning!
Connecting Softstarters PSE18...PSE370 Inside Delta will cause dam-
age to the equipment, and there is a risk of death or serious injury.
Warning!
Before connecting the Softstarters PSE size 18...PSE170 to opera-
tional supply voltage for the first time, the control supply voltage must
be turned on to ensure that the by-pass relays are in the open posi-
tion. This is necessary to avoid unintentional starting of the equipment
during the connection.
1.
Be aware of the ambient temperature. Derating is required above 40 °C
(104 °F). See chapter 3.6.
2.
Mount the softstarter according to Chapter 4 Mounting.
Caution
!
Hazardous voltage. Will cause death or serious injury. Turn off and
lock out all power supplying this device before starting work on this
equipment.
3.
Connect the terminals 1L1, 3L2 and 5L3 to the operational voltage on the
power supply line side.
4.
Connect the terminals 2T1, 4T2 and 6T3 to the motor.
Warning!
Capacitors for power factor compensation are not allowed between
the softstarter and the motor, since this can cause current peaks
which can damage the thyristors in the softstarter. If such capaci-
tors are to be used, they should be connected on the line side of the
softstarter.
PSE
PSE
In Line
Inside Delta