ABB PSE 18 Installation And Commissioning Manual page 91

Hide thumbs Also See for PSE 18:
Table of Contents

Advertisement

Status
Fieldbus fault
Red Fault LED steady lighting, and LCD
event code EF40.
See chapter 6.1.2.1 about LED status indi-
cators activation for faults and protections.
Ready
Run
Protection
Low supply voltage
Red Fault LED steady lighting, and LCD
event code EF50.
See chapter 6.1.2.1 about LED status indi-
cators activation for faults and protections.
Ready
Run
Protection
High current fault
Red Fault LED steady lighting, and LCD
1
event code EF6x
.
See chapter 6.1.2.1 about LED status indi-
cators activation for faults and protections.
Ready
Run
Protection
SF = Softstarter fault
EF = External fault
P = Protection
x = phase number, 4 indicates multiple or unknown phase
1
Possible cause
Fault on fieldbus connection or Field-
BusPlug Accessory.
Fault
Fieldbus communication is not working.
PLC is not running.
Fieldbus Control is enabled on a non-field-
bus application.
The control supply voltage is too low on
terminals 1 and 2.
Short power loss on the control supply
network.
Fault
Operational current higher than 8 x I e .
Fault
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
Solution
Check that the correct type of
FieldBusPlug accessory is used. See
Chapter 8 or contact your ABB Sales
Office.
Check that the connection of the
FieldBusPlug is correct. See chapter
3.2.
Check the connection of the fieldbus
accessory.
Perform a reset on any active event.
See chapter 6.1.5 Reset of tripping
events.
Check that the correct type of
FieldBusPlug accessory is used. See
Chapter 8 or contact your ABB Sales
Office.
Check that the connection of the
FieldBusPlug is correct. See chapter
3.2.
Check the connection of the fieldbus
accessory.
Check PLC configuration.
Possible Fieldbus fault.
Put PLC in run mode.
Check PLC configuration.
Set Fieldbus Control parameter to
OFF.
Check and correct control supply
voltage.
Check control supply network for
short interruptions.
Check if the motor is locked or running
stiff.
Check the bearings in the motor and
connected equipment.
Check if the load on the motor is too
heavy.
Check isolation on the motor wind-
ings.
Replace the motor.