Fieldbus Address; Download Parameter - ABB PSE 18 Installation And Commissioning Manual

Hide thumbs Also See for PSE 18:
Table of Contents

Advertisement

Figure 7.28: Fieldbus Address parameter
displayed
Figure 7.29: Download Parameter displayed

7.5.12.1 Fieldbus Address

The parameter Fieldbus Address allows setting of address for the fieldbus com-
munication.
The setting range for the fieldbus address is 0...255. If the address is set to 255,
the address stored in internal memory of the fieldbus plug will be used. See docu-
mentation for the fieldbus plug for more details on address setting.
It is possible to read and set this parameter via the keypad when Fieldbus Control
is set to On or OFF.
Changing this parameter will automatically reset the fieldbus interface and the new
address will be active. If PLC was communicating with the old address, the PLC
needs to be re-configured.
Display
Default
value
255

7.5.12.2 Download Parameter

This parameter allows for blocking parameter download from the fieldbus. Note
that download of parameters works differently for different fieldbus protocols. See
documentation for the protocol used.
It is possible to read and set this parameter via the keypad when Fieldbus Control
is set to On or OFF.
Display
Default
value
dPon
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
Setting
Description
range
0...255
Fieldbus Address
Setting
Description
range
dPoF/dPon
Download Parameter enabled.
Download Parameter blocked.
Chapter 7
71