Functional Earth, Terminal 14 - ABB PSE 18 Installation And Commissioning Manual

Hide thumbs Also See for PSE 18:
Table of Contents

Advertisement

1
Figure 5.9: Tightening torques and wire area
36
Chapter 5
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201

5.2.4.2 Functional earth, terminal 14

Connect the cable to an earthing point close to the softstarter. The cable should
be as short as possible. A suitable earthing point would be next to the softstarter
on the mounting plate, as shown in figures 5.8 and 5.9. The mounting plate
should also be earthed.
This is not a protective earth, it is a functional earth. The earthing cable should be
as short as possible. Maximum length 0.5 m.
2
1 4
Figure 5.8: Terminal for functional earth
2
3
4
5
6
7
8 9 10 11 12 13
3,5 x 0,6 mm
M3
14
(0.138 x 0.24 in)
0,5 Nm - 4,3 lb.in
AWG 24 ... 12
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents