ABB PSE 18 Installation And Commissioning Manual page 13

Hide thumbs Also See for PSE 18:
Table of Contents

Advertisement

Exit
Select
Reset
A
Exit
Select
Reset
Figure 2.3:
Configuration of the parameter Rated Current.
If disabled, press any key to activate the light
A
in the display. Enter the application setting by
pressing the Select key a second time.
B
Press select again to enable editing of the I e
parameter. This is indicated by a flashing value.
Increase or decrease the value by pressing the
C
Up or Down keys repeatedly. Holding the key
down will speed up the change. Press the Exit
key to abort change.
D
When the rated current of the motor is
reached, press the Select key again to save.
If needed, continue to set other parameters
according to the application following the
same procedure.
Press the Exit key to return to the top level.
Exit
Select
Reset
B
Exit
Select
C
Reset
Exit
Select
Reset
D
Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
5.
Connect control supply voltage to terminals 1 and 2 (100-250 V 50/60 Hz).
6.
Connect the functional earth to terminal 14, with an earthing point close to
the softstarter.
The earthing is not a protective earth, it is a functional earth. The earthing
cable should be as short as possible. Maximum length 0.5 m. The earthing
cable should be connected to the mounting plate, which should also be
earthed.
7.
Connect the start, stop and other control circuits including the analog out to
the terminals, 8, 9, 10, 11, 12, 13 if needed. This section is using an internal
24 V DC. Do not feed with any external voltage.
Warning!
Do not connect an external voltage to the control terminals 8, 9, 10,
11, 12, 13 and 14. Failure to observe the above may damage the softs-
tarter and the warranty may no longer be valid.
8.
Connect terminals 3, 4, 5, 6 and 7 when using the signal output relays. These
are potential free contacts for maximum 250 V AC, 1,5 A AC-15. Make sure
you are using the same voltage level within this terminal section.
Warning!
The same external voltage (maximum 24 V DC or maximum 250 V
AC) must be connected to the output relay terminals 3, 4, 5, 6 and 7.
Failure to observe the above may damage the softstarter and the war-
ranty may no longer be valid.
9.
Switch ON the control supply voltage U s , terminals 1 and 2.
10. Continue to configure parameter I e as described in figure 2.3. Complete
information about configuration is available in Chapter 6 Human-Machine
Interface (HMI) and Chapter 7 Functions and configuration.
11. Switch ON the operational voltage U e . The green "Ready" LED will turn solid.
12. Give start command to the softstarter.
Caution!
Depending on the two phase control, a connected motor terminal
always carries live hazardous voltage. Do not touch terminals when
voltage is applied. Output terminals will have live voltage even when
the device is OFF. This can cause death or serious injury.
Chapter 2
13