Advertisement

Installation and mounting

5.6 Fixing a vertical busbar run

5.6
Fixing a vertical busbar run
Fixing bracket and fixed point
The fixing bracket for vertical installation is dimensioned for carrying the weight of the busbar
run for a storey height of h = 3.40 m to 3.90 m. For this reason, the complete type code and
the use of tap-off units must be considered when determining the type.
The following applies for the fixing bracket at a storey height of h = 3.40 m to h = 3.90 m:
Power transmission
Power distribution
At least one tap-off unit per floor
1)
Determination of the type of the fixed point is oriented around attachment to single systems
or double systems:
Size
LX.01 to LX.07 (single systems)
LX.08 to LX.10 (double systems)
Fixing brackets for vertical installation
78
Size
LX.01 to LX.07 (single
systems)
LX.08 to LX.10 (double
systems)
LX.01 to LX.07 (single
1)
systems)
LX.08 to LX.10 (double
systems)
Unit quantity
1
2
1
2
Type
LX-BV1FP1
LX-BV1FP2
Fixing brackets with fixed point for vertical
installation
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
Type
LX.....-BV1
LX.....-BV1
LX.....-BV1-AK
LX.....-BV1-AK