Siemens SIVACON 8PS Configuration Manual page 102

Busbar trunking system. configuring with lx system. low-voltage power distribution and electrical installation technology
Hide thumbs Also See for SIVACON 8PS:
Table of Contents

Advertisement

Configuration
6.1 Basic knowledge for configuring
Fitting the tap-off units with fuse switch disconnectors
● Manually operated fuse switch disconnector
● in 3 or 4-pole designs
● With built-in fuse holder in accordance with IEC or BS standard.
● Rated operating voltage U
Rated currents, sizes and fuse standards
I
1)
e
[A]
125
125
250
250
400
400
630
630
IEC International Electrotechnical Commission
BS
1)
100
Size
Fuse switch disconnector with
fuse holder in accordance with
1
IEC
1
BS
2
IEC
2
BS
3
IEC
3
BS
4
IEC
4
BS88
British Standard
Reduced current value specifications caused by built-in units and mounting position are
described in the technical data.
= 400 V
e
Fuses
I
cf
[kA]
NH00
100
BS88
80
NH1
100
BS88
80
NH2
100
BS88
80
NH3
100
BS88
80
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02