Trunking Units Lxc - Siemens SIVACON 8PS Configuration Manual

Busbar trunking system. configuring with lx system. low-voltage power distribution and electrical installation technology
Hide thumbs Also See for SIVACON 8PS:
Table of Contents

Advertisement

Technical data
7.9 Trunking units LXC..41 (copper)
7.9
Trunking units LXC..41 (copper)
System-specific data
Rated current
Conductor impedance
At 50 Hz and + 20 °C
busbar temperature
At 50 Hz and final heating
of busbars
for 5-pole systems (PE)
under fault conditions
acc. to EN 60439-2
Zero impedance
for 5-pole systems (PE)
acc. to DIN EN 60909-0 /
VDE 0102
Short-circuit rating
Rated short-time
withstand current
Rated impulse withstand
current
Conductor material
No. of busbars
Conductor cross section
Equivalent copper cross
section
Weights
140
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
rms value t = 1 s
Peak value
L1, L2, L3
PEN
LXC
0141
I
A
1000
1)
e
R
mΩ/m
0.065
20
X
mΩ/m
0.027
20
Z
mΩ/m
0.071
20
R
mΩ/m
0.083
1
X
mΩ/m
0.027
1
Z
mΩ/m
0.087
1
R
mΩ/m
0.109
F
X
mΩ/m
0.079
F
Z
mΩ/m
0.134
F
R
mΩ/m
0.196
0
X
mΩ/m
0.121
0
Z
mΩ/m
0.230
0
I
kA
38
cw
I
kA
80
pk
Copper
4
A
mm
292
2
A
mm
1240
2
kg/m
17.9
0241
0341
0441
1250
1400
1600
2)
0.051
0.044
0.037
0.031
0.020
0.026
0.059
0.048
0.045
0.065
0.055
0.045
0.031
0.020
0.026
0.072
0.059
0.051
0.088
0.077
0.065
0.081
0.081
0.065
0.120
0.121
0.092
0.162
0.142
0.122
0.127
0.121
0.095
0.206
0.187
0.154
50
57
60
110
125
132
4
4
4
386
442
586
1334
1460
1604
21.6
24.1
29.7
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
0541
2000
3)
4)
0.027
0.013
0.030
0.035
0.013
0.037
0.049
0.047
0.068
0.093
0.067
0.114
75
165
4
712
1847
35.3