Fire Barrier - Siemens SIVACON 8PS Configuration Manual

Busbar trunking system. configuring with lx system. low-voltage power distribution and electrical installation technology
Hide thumbs Also See for SIVACON 8PS:
Table of Contents

Advertisement

5.4

Fire barrier

Positioning and installing the fire barrier
The fire barrier must be positioned in such a way that it is always in or in front of the fire
wall/fire ceiling. The maximum fixing distances must be observed here (see Case 1 to 5).
Centre of the fire barrier = centre of fire wall/centre of fire ceiling is not absolutely necessary.
Flush finishing with the fire wall/fire ceiling is permissible (see Case 2), or the fire barrier can
also be positioned on the fire wall/fire ceiling (see Case 3). Undefined mounting positions are
not permitted (Case 6).
Case 1: Fire barrier in the centre of the fire wall/fire ceiling
Case 2: Fire barrier finishes flush with the fire wall/fire ceiling
Case 3: Fire barrier in front of the fire wall/fire ceiling
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
700
≤ 820
≤ 820
700
≤ 820
≤ 820
700
≤ 820
≤ 820
Installation and mounting
5.4 Fire barrier
73