Trunking Units Lxa - Siemens SIVACON 8PS Configuration Manual

Busbar trunking system. configuring with lx system. low-voltage power distribution and electrical installation technology
Hide thumbs Also See for SIVACON 8PS:
Table of Contents

Advertisement

Technical data
7.2 Trunking units LXA..30 (aluminium)
7.2
Trunking units LXA..30 (aluminium)
System-specific data
Rated current
Conductor impedance
At 50 Hz and + 20 °C
busbar temperature
At 50 Hz and final heating
of busbars
for 5-pole systems (PE)
under fault conditions
acc. to EN 60439-2
Zero impedance
for 5-pole systems (PE)
acc. to DIN EN 60909-0 /
VDE 0102
Short-circuit rating
Rated short-time
withstand current
Rated peak withstand
current
Conductor material
No. of busbars
Conductor cross section
Equivalent copper cross
section
Weights
126
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
Resistance
Reactance
Impedance
rms value t = 1 s
Peak value
L1, L2, L3
PE = enclosure
LXA
0130
I
A
0800
e
R
mΩ/m
0.117
20
X
mΩ/m
0.028
20
Z
mΩ/m
0.120
20
R
mΩ/m
0.146
1
X
mΩ/m
0.028
1
Z
mΩ/m
0.149
1
R
mΩ/m
0.223
F
X
mΩ/m
0.140
F
Z
mΩ/m
0.263
F
R
mΩ/m
0.434
0
X
mΩ/m
0.363
0
Z
mΩ/m
0.566
0
I
kA
25
cw
I
kA
53
pk
Aluminium
3
A
mm
292
2
A
mm
948
2
kg/m
9.6
0230
0430
0530
1000
1250
1600
0.084
0.056
0.036
0.031
0.024
0.017
0.090
0.061
0.040
0.106
0.07
0.043
0.031
0.024
0.017
0.110
0.074
0.046
0.214
0.180
0.116
0.139
0.114
0.095
0.255
0.213
0.150
0.473
0.428
0.275
0.354
0.293
0.250
0.591
0.519
0.372
35
50
60
70
110
132
3
3
3
386
586
946
948
1018
1135
10.6
13.3
17.8
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
0630
2000
0.027
0.009
0.035
0.034
0.009
0.029
0.110
0.071
0.131
0.277
0.195
0.338
75
158
3
1192
1348
21.8