Configuration
6.2 Configuring the busbar run layout
Vertical busbar run layout between junction unit and end cap, Case 2
● Expansion compensation unit is not required in the topmost sub-run to the end cap.
● Position further expansion compensation units in the centre between the fixed points.
L1
L
D
FP
EF
Examples of power distribution with LXA...., (LXC....)
Run length L
[m]
≤ 50 (≤ 60)
≤ 100 (≤ 120)
≤ 150 (≤ 180)
≤ 200 (≤ 240)
116
Max. permissible sub-length
Total run length
Expansion compensation
Fixed point (type: LX-BVFP..)
End cap
Number of fixed points (FP)
1
2
3
4
Configuration Manual, 10/2011, A5E02194899-02
Number of expansion
compensation units (D)
0
1
2
3
SIVACON 8PS - Configuring with LX system