Siemens SIVACON 8PS Configuration Manual page 117

Busbar trunking system. configuring with lx system. low-voltage power distribution and electrical installation technology
Hide thumbs Also See for SIVACON 8PS:
Table of Contents

Advertisement

Vertical busbar run layout between two junction units, Case 1
● Always position the expansion compensation units in the centre between the fixed points.
L1
L
D
FP
EF
Examples of power transmission with LXA...., (LXC....)
Run length L
[m]
≤ 6 (≤ 6)
≤ 25 (≤ 40)
≤ 50 (≤ 80)
≤ 75 (≤ 120)
Examples of power distribution with LXA...., (LXC....)
Run length L
[m]
≤ 6 (≤ 6)
≤ 50 (≤ 60)
≤ 100 (≤ 120)
≤ 150 (≤ 180)
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
Max. permissible sub-length
Total run length
Expansion compensation
Fixed point (type: LX-BVFP..)
End cap
Number of fixed points (FP)
2
2
3
4
Number of fixed points (FP)
2
2
3
4
6.2 Configuring the busbar run layout
Number of expansion
compensation units (D)
0
1
2
3
Number of expansion
compensation units (D)
0
1
2
4
Configuration
115