Tap-Off Units - Siemens SIVACON 8PS Configuration Manual

Busbar trunking system. configuring with lx system. low-voltage power distribution and electrical installation technology
Hide thumbs Also See for SIVACON 8PS:
Table of Contents

Advertisement

Technical data

7.19 Tap-off units

7.19
Tap-off units
Standards and regulations
Resistance to extreme climates
Ambient temperature
Degree of protection
Trunking unit material
Colour of tap-off units
Dimensions
Rated insulation voltage U
Overvoltage category/
pollution degree
Rated operating voltage U
Rated frequency
Tap-off units with circuit breaker
Rated current I
e
Max. permissible operating current I
1)
max
Conditional short-circuit rating I
Connectable cross sections (CU)
L1, L2, L3
N, PE, ISO-PE
Bolted connection
156
DIN EN 60439-1/VDE 0660-500
DIN EN 60439-2/VDE 0660-502
Damp heat, constant, acc. to IEC 60068-2-78
Damp heat, cyclic, acc. to IEC 60068-2-30
°C
–5/+40/+35 (min./max./24-hour average)
IP54, IP55 on request
Sheet steel, painted
RAL 7035 (light grey)
See also Chapter Auto-Hotspot
V AC
690
i
III/3 acc. to DIN EN 60947-1/VDE 0660-100
V AC
400
e
Hz
50
Size 1
A
50; 63; 80; 100;
125; 160; 200; 250
A
in accordance with
r
I
e
kA
65
cc
mm
1 x 50...150
2
2 x 25...70
mm
1 x 50...150
2
2 x 25...70
M8
Size 2
Size 3
315
400
630 —
315
380
520
65
1 x 70...240
2 x 70...120
1 x 70...240
2 x 70...120
315 A: M8
400 A: M10
630 A: M12
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
Size 4
800
;
2)
1000
;
2)
1250
in accordance
with I
e
100
1 x 70...240
4 x 70...240
1 x 70...240
4 x 70...240
M12