Configuration between 2 junction units
①
Run length L
[m]
≤ 30
≤ 60
≤ 90
Note
A maximum permissible run length of 30 m applies for horizontal run layouts with expansion
compensation between two fixed points.
Configuration between junction unit and universal busbar connection unit
①
②
③
④
L ≤ 15 m
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
Fixed point
Junction unit
Fixed point (here: LX-BHF)
Universal busbar connection unit (AS)
Last trunking unit before the universal busbar connection unit
Number of fixed points
0
2
3
6.2 Configuring the busbar run layout
Number of expansion
compensation units
0
1
2
Configuration