3.2

Performance capability of the individual SIVACON 8PS systems

Performance overview for the CD-K, BD01 and BD2 systems
The following tables present an overview of the performance capabilities of the individual
SIVACON 8PS systems:
Table 3- 1
Performance data
Parameter
Rated current I e [A]
Rated operational
voltage [V AC]
Frequency [Hz]
No. of active
conductors
Degree of protection
Max. ambient
temperature [°C]
Max. ambient
temperature [°C]
Mounting position
Length [m]
Tap-off points on one
side
Tap-off points on two
sides
Tap-off units
Conductor material
Enclosure
Fire load [kWh / m]
Special
features/communicatio
n capability
SIVACON 8PS - Configuring with LX system
Configuration Manual, 10/2011, A5E02194899-02
3.2 Performance capability of the individual SIVACON 8PS systems
CD-K
30
40
2 x 25
2 x 40
400
50 ... 60
2, 3, 4, 2 x 4
(PE = enclosure)
Up to IP55
+40
-5
Edgewise
2
3
Every 0.5 m or 1.0 m
Every 0.5 m or 1.0 m
Up to 16 A
Insulated CU conductor
Sheet steel enclosure, painted
0.1 ... 0.48
BD01
40
63
100
125
160
400
50 ... 60
4
(PE = enclosure)
Up to IP55
+40
-5
Edgewise, flat
(tap-off points pointing down)
2
3
Every 0.5 m or 1.0 m
Up to 63 A
Insulated CU or AL conductor
Sheet steel enclosure, painted
0.76
Lighting control
Product description
BD2A
BD2C
160 ... 400
160 ... 400
500 ... 1000
500 ... 1250
690
50 ... 60
5
Up to IP55
+40
-5
Edgewise,
flat and vertical
0.5 ... 3.25
Every 0.25 m or 0.5 m offset to
each other
Up to 530 A
AL or CU rails
Sheet steel enclosure, painted
0.6 ... 0.67
(without tap-off points)
Lighting control
Remote switching and
signalling
Consumption recording
17