Table VII: Hazardous Area Certifications
Certification
Notified Body
Option
®
8
x
-04 or -15
ATEX
-03 or -04 or -20
IECEx
-06 or -22
KOSHA
c
WARNINGS:
1. In order to maintain the explosionproof certifications do not remove or loosen covers during operation.
2. To avoid the possibility of static discharge clean only with a damp cloth.
3. The positioner must be connected to suitable rated intrinsically safe equipment, and must be installed in accordance with intrinsically safe installation standards.
User instructions - Digital Positioner 3200MD LGENIM0059-01 10/08
®
Approval
Explosionproof:
Class I, Div 1, Groups B,C,D
-10
Dust Ignition Proof:
Class II, III, Div 1, Groups EFG
Intrinsically Safe:
Class I, II, III, Div 1, Groups A,B,C,D
Class 1, Zone 0, AEx ia IIC
-10
Non-Incendive:
-10
Class I, Div 2, Groups A,B,C,D
Explosionproof:
Class I, Div 1, Groups B,C,D
-10
Class II, Div 1, Groups E,F,G
Class III
Intrinsically Safe:
Class I, II, III, Div 1, Groups A,B,C,D
10
Non-Incendive:
10
Class I, II, Div 2, Groups A,B,C,D
Explosionproof (Flameproof):
II 2 GD
-07
Ex d IIB + H
2
Ex tD A21 T95ºC
Intrinsically Safe:
II 1 G
Ex ia IIC
Non-Incendive:
II 3 G
Ex nL nA IIC
Explosionproof (Flameproof):
-16
Ex d IIB + H
2
Intrinsically Safe:
Ex ia IIC
-21
Explosionproof (Flameproof):
-06
BR-Ex d IIB + H
2
Intrinsically Safe:
BR- Ex ia IIC
Explosionproof (Flameproof)
-07
Ex d IIB + H
2
Entity Parameters
Not Applicable
(See Warning No. 1, 2)
Vmax = 30 Volts
Imax
= 100mA
Pmax = 800mW
Ci
= 30 nF
Li
= 0
(refer to control drawing No.
198736)
(See Warning No. 2,3)
Install per NEC Article
501-4 when barriers are
(See Warning No. 2)
not used.
Not Applicable
(See Warning No. 1, 2)
Vmax = 30 Volts
Imax
= 100mA
Pmax = 800mW
Ci
= 30 nF
Li
= 0
(See Warning No. 2, 3)
(refer to control drawing No.
198736)
Not Required
(See Warning No. 2)
Not Required
(See Warning No. 1, 2)
Ui = 30 Volts
Ii = 100mA
Pi = 800mW
Ci = 30 nF
Li = 0
Co = 36 nF
(See Warning No. 2, 3)
Not Required
(See Warning No. 2)
Not Required
(See Warning No. 1, 2)
Ui = 30 Vdc
Ii = 100mA
(See Warning No. 2, 3)
Pi = 0.8W
Ci = 30 nF
Li = 0
Not Required
(See Warning No. 1, 2)
Ui = 30 Vdc
Ii = 100mA
(See Warning No. 2, 3)
Pi = 800mW
Ci = 30 nF
Li = 0
Co = 36 nF
Not Required
(See Warning No. 1, 2)
Enclosure
Temperature Code
Rating
NEMA
T6 T
≤ = 60ºC
4X
amb
T4 T
≤ = 85ºC
NEMA
amb
T5 T
≤ = 55ºC
4X
amb
T4 T
≤ = 85ºC
NEMA
amb
T5 T
≤ = 55ºC
4X
amb
Type
-25º ≤ Ta ≤ +40ºC
4X
Type
T4 T
≤ = 80ºC
4X
amb
Type
T4 T
≤ = 80ºC
4X
amb
T5 (T = -40ºC to + 80ºC)
IP65
T4 (T
-40ºC to + 85ºC)
IP65
amb
T5 (T
-40ºC to + 55ºC)
amb
T4 T
-40ºC to + 85ºC)
IP65
amb
T5 T
-40ºC to + 55ºC)
amb
T5 (T
-20ºC to + 55ºC)
IP65
amb
T5 (T
-40ºC to + 80ºC)
amb
T4 (T
-40ºC to + 85ºC)
IP65
amb
T5 (-40ºC ≤ Ta ≤ + 80ºC)
IP65
T5 (-40ºC ≤ Ta ≤ + 55ºC)
IP65
T4 (-40ºC ≤ Ta ≤ + 85ºC)
T5 (T = -40ºC to + 80ºC)
IP65
5