8.
ACTIVATION/CONFIRMATION EVENT HANDLING
Activation status:
l
Activation indicator on (flashing if there is no confirmation)
l
Confirmation indicator on (only if there is confirmation signal)
l
Activation events are shown on the LCD as the figure
l
Acknowledge/Silence indicator flashing
l
Buzzer turns on
How to handle:
1.
Press Acknowledge/Silence to silence the buzzer:
Under Level 1 interface, a login interface pops out automatically. Enter
l
Level 2/3 password and press "OK" to return back to fire alarm window
then press "Acknowledge/Silence". Now,
Buzzer is mute.
-
The Acknowledge/Silence indicator turns off.
-
l
Under Level 2/3 interface,
-
Buzzer is mute
-
The Acknowledge/Silence indicator turns off.
2.
Find out the activation/confirmation location from LCD.
3.
Go to the site to handle it if necessary.
4.
Confirmation indicator turns off when confirmation signal disappears. When
activation signal disappears, press "Reset" to turn off the activation indicator
and the controller return to normal.
Note:
When an activation/confirmation event occurs together with another
-
event of higher priority, activation/confirmation event cannot be
displayed automatically. Enter the activation/confirmation window
manually (see "real-time query" function) to handle it.
Press "←" to switch between fire alarm window and activation window.
-
Operating Manual of FC18 Controller
Fig.8-1activation interface
Page: 25/63