FC1861/FC1862/FC1863
Controller
Operating manual
Smart Infrastructure
A5Q00041121

Advertisement

Table of Contents
loading

Summary of Contents for Siemens FC18 Series

  • Page 1 FC1861/FC1862/FC1863 Controller Operating manual Smart Infrastructure A5Q00041121...
  • Page 2: Table Of Contents

    Operating Manual of FC18 Controller TABLE OF CONTENTS CHAPTER 1 SYSTEM OVERVIEW ·················································································································· 3 FEATURES ······································································································································· 3 TECHNICAL DATA ····························································································································· 4 DIMENSIONS···································································································································· 5 COMPATIBLE EQUIPMENT LIST ··········································································································· 5 SYSTEM STRUCTURE ······················································································································· 6 CHAPTER 2 INSTALLATION ······················································································································· 8 INSTALLATION ·································································································································· 8 CONNECTION DIAGRAM ····················································································································...
  • Page 3 Operating Manual of FC18 Controller APPENDIX 2 OPERABLE ITEM LIST············································································································ 62 APPENDIX 3 DEVICES GROUPING TABLE ··································································································· 64 APPENDIX 4 RULES FOR LOGIC EXPRESSION ···························································································· 65 APPENDIX 5 INPUT METHOD ···················································································································· 67 APPENDIX 6 “STICKER METHOD”EASY FOR COMMISSIONING ··································································· 68 APPENDIX 7 GLOSSARY ··························································································································...
  • Page 4: Chapter 1 System Overview

    Operating Manual of FC18 Controller CHAPTER 1 SYSTEM OVERVIEW The FC186x series controllers have three kinds: FC1861 controller with 2 line card, max. 504 points FC1862 controller with 4 line card, max. 1008 points FC1863 controller with 6 line card, max. 1512 points 1.
  • Page 5: Technical Data

    Operating Manual of FC18 Controller TECHNICAL DATA Table 1-1 Item Parameter Max. No. of line cards Max. No. of devices 2016 LCD screen 320×240 pixels,backlit No. of programmable input/output on mainboard No. of NAC (0.5mA @24VDC) Max. history records 10000 Max.
  • Page 6: Dimensions

    Operating Manual of FC18 Controller DIMENSIONS (In: mm) Fig. 1-1 Dimensions COMPATIBLE EQUIPMENT LIST Table 1-2 Type Description FDT181 Heat detector FDO181 Smoke detector FDM181 Manual call point FDCI181-2 Input module FDCIO181-2 Input/output module FT1810 Floor repeater display FDCL181 Isolator FT1811 Addressable Mimic Driver FTM1811...
  • Page 7: System Structure

    Operating Manual of FC18 Controller SYSTEM STRUCTURE Up to 16 FC18 controllers can be networked together. Any controller can be set as master controller to supervise devices connected with its slave controller and its own. Up to 20000 devices can be connected in one system. Fig.
  • Page 8 Operating Manual of FC18 Controller Main Unit Terminal Board of main unit Terminal Board of Line Card Line Card & Plate Breaker Power Supply10A Battery Fig. 1-3 Internal structure Page: 7/70...
  • Page 9: Chapter 2 Installation

    Operating Manual of FC18 Controller CHAPTER 2 INSTALLATION INSTALLATION Fig. 2-1 Installation size (In: mm) Note: Installation must comply with the local regulation! Procedure: Choose a place where is dry, clean, flat and firm for controller installation. Choose a proper installation location to make sure the front door can be opened smoothly. Mark 4 installation holes with pen on the wall for drilling.
  • Page 10: Connection Diagram

    Operating Manual of FC18 Controller CONNECTION DIAGRAM MB Link Ext. Pwr. Mntr. Pwr. Status Printer Pwr. MB Pwr. CAN End FCnet ID Printer Reset Int. Output 1-8 CPU COM Int. Input 1-8 Int. ID Printer COM LC-1 LC-2 Int. COM LC COM DL RS485 图...
  • Page 11 Operating Manual of FC18 Controller Fig. 2-3 Terminal board of main unit Table-2-2 Sign Description Connect to “MB Link” port on main unit MB link /FCnet(upside) Int. COM Reserved LC COM Connect to line card for communication LC Pwr Connect to line card for power supply Ext.
  • Page 12 Operating Manual of FC18 Controller Note: In loop mode, wires from BP1 must end at AP1; wires from BS1 must end at AS1. The connection of field devices (except FDCL181 isolator) is polarity free. Fig. 2-5 Line card connection diagram (the same for other line) Fig.
  • Page 13: Dip-Switch

    Operating Manual of FC18 Controller Fig. 2-10 Interlocking panel connection diagram (the same for other channels) Note: the load range of each output is 24VDC, 600Ω – 1.2kΩ DIP-SWITCH There is a 8-digit Dip-switch FCnet ID (Fig. 2-2) on main unit. The 1-6 digit of Dip-switch is available, used to set 1-32 address of main unit.
  • Page 14: Power Supply

    Operating Manual of FC18 Controller POWER SUPPLY Stable and reliable DC output Auto switch between main power and battery Alternative AC power switch Charge and protect battery Monitor main power, battery, trouble status Auto recoverable current protection circuit for overload and short circuit Switch between 220VAC and 110VAC Fig.
  • Page 15 Operating Manual of FC18 Controller Table 2-7 Specification of power supply Input voltage 110/220 VAC Input frequency 60/50 Hz Output voltage 24 VDC Output current AC fuse capacity 110VAC: 6A 220VAC:3A DC fuse capacity Operating temperature 0 ~ +40℃ when it is over 40℃, output power will reduce half Storage temperature -20 ~ +60℃...
  • Page 16: Chapter 3 Operation

    Operating Manual of FC18 Controller CHAPTER 3 OPERATION 1. INTERFACE Fig. 3-1 Operation panel ① The LCD backlight automatically turns off within the preset time in the idle mode; the preset time can be adjusted in the parameter setting. Press any key turns on the LCD again. Printer ②...
  • Page 17 Operating Manual of FC18 Controller Supervision: On when supervision signal is detected; off when the signal disappears and “reset” is pressed. ¹ System trouble: On when system hardware/software is faulty. ¹ Trouble: On when trouble happen; off when trouble is resolved. ¹...
  • Page 18 Operating Manual of FC18 Controller until master is reset. Interlocking panel ⑤ The interlocking panel has 8 output channels. Each channel has indicators to indicate trouble, activation and confirmation status. Each channel can be controlled by Activation/Deactivation button manually. Only level 2&3 user can access.
  • Page 19: Lcd Window

    Operating Manual of FC18 Controller 2. LCD WINDOW ① ② ③ Fig. 3-2 Display screen FC18 controller has 3 windows which are menu window (1), browser window (2) and statistics window (3). Menu window: ① ¹ Display operation menus according to different user levels. Items for Level 3 are shown as follows. Main menu Event Browse...
  • Page 20 Operating Manual of FC18 Controller ② Browser window: ¹ Display real-time events: fire alarm, activation & confirmation, trouble, supervision, disable, test and walk-test. ¹ Display node tree. ¹ Priority of display: fire alarm→ activation & confirmation→ supervision→ disable→ trouble→ test/walk-test→ normal. ③...
  • Page 21: User Level

    Operating Manual of FC18 Controller 3. USER LEVEL FC18 has 3 user levels. User level is displayed at the lower right corner of the screen (Fig. 3-2) Users of different levels have their own operation interfaces. Table 3-1 user level list Item Level 1 Level 2...
  • Page 22: Login

    Operating Manual of FC18 Controller 3.1 Login Press “Menu” to browse the main menu. Display main menu. Press”→” to select “Login”, then press “OK”. Password entry window pops out. Fig. 3-3 Enter the password for Level2/3 and press “OK”. Login as a Level 2/3 user if the password entered is correct. (Press “←”...
  • Page 23: Status Types

    Help Login l Main power supply indicator on l Auto/Manual indicator on System Normal SIEMENS Building l No events taken place such as alarm/activation, trouble, supervision, SIEMENS disable, test, walk-test etc. l LCD shown as figure or backlight <2008-08-08 08:08:08>...
  • Page 24 Operating Manual of FC18 Controller Activation status: Activation Activation indicator on (flashing when there is no confirmation) 0001 Activation 2008-08-08 10:10:13 Output 1 / 01.005.008 LCD shown as the figure Acknowledge/Silence indicator flashing Buzzer ringing Fig. 4-5 Confirmation status: Confirmation Confirmation indicator on 0001 Confirmation 2008-08-08 10:10:11...
  • Page 25: Fire Alarm Event Handling

    Operating Manual of FC18 Controller FIRE ALARM EVENT HANDLING Fire alarm status: Fire alarm indicator turns on Fire event with customer information shown in the LCD as the figure Acknowledge/Silence indicator flashing NAC activation indicator turns on Buzzer turns on NAC devices activated How to handle: Fig.
  • Page 26: Trouble Event Handling

    Go to the site to trouble-shoot. The trouble indicator turns off when problems are solved. If you cannot solve the problem, please call local Siemens service center. Note: When a trouble occurs together with another event of higher priority, trouble event cannot be displayed automatically.
  • Page 27: Supervision Event Handling

    Operating Manual of FC18 Controller SUPERVISION EVENT HANDLING Supervision status: Supervision indicator turns on Supervision events are shown on the LCD as the figure Acknowledge/Silence indicator flashing Buzzer turns on How to handle: Press “Acknowledge/Silence” to silence the buzzer: Under Level 1 interface, a login interface pops out automatically. Enter Fig.7-1 Level 2/3 password and press “OK”...
  • Page 28: Activation/Confirmation Event Handling

    Operating Manual of FC18 Controller ACTIVATION/CONFIRMATION EVENT HANDLING Activation status: Activation indicator turns on (flashing if there is no confirmation) Confirmation indicator turns on (only when confirmation signal is received) The activation events are shown on the LCD as the figure Acknowledge/Silence indicator flashing Buzzer turns on How to handle:...
  • Page 29: Real-Time Event Query

    Alarm & active Alarm & active Main menu displayed. Trouble System Normal Supervision Disable SIEMENS Building Test SIEMENS Walk-Test Locate <2008-08-08 08:08:08> Press “↓” to select an event type to query then press “OK”. All the queried events will be displayed in the window. Use “↓” /”↑” to browse Fig.
  • Page 30: How To Query Equipment Property

    Operating Manual of FC18 Controller 11. HOW TO QUERY EQUIPMENT PROPERTY Steps: Trouble Select a station, a line or a point and press “→” to pop out a shortcut menu 0002 COMM trouble 2008-08-08 10:10:10 Interlocking Line / 01.005 (Fig. 10-1), then select “Property” and press “OK” to pop out a property 0001 Other 2008-08-08 10:10:08 Property...
  • Page 31: How To Query History

    Operating Manual of FC18 Controller 12. HOW TO QUERY HISTORY FC18 controller (interlocking) contains 11 types of history records which are alarm, trouble, supervision, activation/confirmation, disable, test and walk-test, unconfigure equipment, unknown equipment, inconsistent equipment, exchange equipment. The first six types support advanced query. Steps: Select a station, a line or a point and press “→”...
  • Page 32: How To Disable/Enable

    Operating Manual of FC18 Controller 13. HOW TO DISABLE/ENABLE Function: The controller should be disabled when the house is being decorated or there are device damages or failure. It should be resumed to normal status as soon as the decorating work or repairing is finished. Note: Disabled device cannot send any message to controller.
  • Page 33: How To Activate/Deactivate

    “OK” to display the tree diagram (Fig. 13-3). Search down level by level through stations, lines and points until you find the device you are looking for. Fig.13-2 SIEMENS Buidling Building 1 Controller Power Monitor Line Onboard I/O Press “→”...
  • Page 34: How To Test/Walk-Test

    Operating Manual of FC18 Controller 15. HOW TO TEST/WALK-TEST Function: To identify whether the alarm device is in normal status. Under test/walk-test mode, an alarm will be triggered when there is an alarm event, but the interlocking equipment will not be activated. Make sure the controller is back to normal after the test.
  • Page 35: How To Locate/Stop Locating

    Operating Manual of FC18 Controller 16. HOW TO LOCATE/STOP LOCATING Function: To locate device. Steps to locate: Press “Menu” to browse the main menu (Fig. 15-1). Main menu displayed. Press “→” to select “Brow” submenu (Fig. 15-2). Press “↓” to select “All”, then press “OK”...
  • Page 36: How To Adjust Buzzer Level

    Operating Manual of FC18 Controller 17. HOW TO ADJUST BUZZER LEVEL Function: Turn up or down the buzzer between level 0-7. Level 0 is mute mode. Steps: Press “Menu” to browse the main menu (Fig. 16-1). Main menu displayed. Fig.16-1 Press “→”...
  • Page 37: How To Set Login Time

    Operating Manual of FC18 Controller 18. HOW TO SET LOGIN TIME Function: Under 2/3 level, if there is no operation in preset login time, controller will automatically log out to level 1. Value range: 1-60 minutes. Steps: Press “Menu” to browse the main menu (Fig. 17-1). Main menu displayed.
  • Page 38: How To Set Walk-Test Time

    Operating Manual of FC18 Controller 19. HOW TO SET WALK-TEST TIME Function: Controller being tested will restore to normal status automatically after the preset walk-test time. Value range: 1-60 min. Steps: Press “Menu” to browse the main menu (Fig. 18-1). Main menu displayed.
  • Page 39: How To Set Lcd Closing Time

    Operating Manual of FC18 Controller 20. HOW TO SET LCD CLOSING TIME Function: LCD turns off if there is no operation or event during the preset LCD closing time. Press any key to turn on the back light. Value range: 1-60 min.
  • Page 40: How To Modify Time

    Operating Manual of FC18 Controller 21. HOW TO MODIFY TIME Function: To modify system time. Steps: Press “Menu” to browse the main menu (Fig. 20-1). Main menu displayed. Fig.20-1 Press “→” to pop out the "Tool" submenu (Fig.20-2). Select “Set Time" and press “OK”...
  • Page 41: How To Check System

    Operating Manual of FC18 Controller 22. HOW TO CHECK SYSTEM Function: To check whether the LCD, indicators, printer and the buzzer can work normally. Steps: Press “Menu” to browse the main menu (Fig. 21-1). Main menu displayed. Fig.21-1 Press “→” to pop out the "Tool" submenu (Fig.21-2). Press "↓" to select “Check System"...
  • Page 42: How To Save Configure

    Operating Manual of FC18 Controller 23. HOW TO SAVE CONFIGURE Function: Save changes permanently, otherwise the changes will be lost when the system is restarted. Steps: Press “Menu” to browse the main menu (Fig. 22-1). Main menu displayed. Fig.22-1 Press “→” to pop out the "Conf" submenu (Fig.22-2). Press "↓" to select “Save Configure"...
  • Page 43: How To Edit Parameter

    Operating Manual of FC18 Controller 24. HOW TO EDIT PARAMETER Function: To modify parameters in system. See Appendix table 1 for details. Steps: Press “Menu” to browse the main menu (Fig. 23-1). Main menu displayed. Fig.23-1 Press “→” to select “Brow” submenu (Fig. 23-2). Press “↓” to select the item which contains the equipment whose parameters need to be modified, and then press “OK”.
  • Page 44: How To Create/View Logic

    Operating Manual of FC18 Controller 25. HOW TO CREATE/VIEW LOGIC Function: To create/view logic expression among detection group, supervision group and control output group. Steps: Press “Menu” to browse the main menu (Fig. 24-1). Main menu displayed. Press “→” to select “Brow” submenu (Fig. 24-2). Select "All" and then press “OK”.
  • Page 45: How To Edit/Delete Logic

    <2008-08-08 08:08:08> Note: The saved change takes effect immediately. Are you sure to delete logic? SIEMENS The change can only be applied to the selected controller. <OK> or <CANCEL> "0" don’t need to be input manually in expressions because the system will add it automatically.
  • Page 46: How To Assign Group/ Frt

    Operating Manual of FC18 Controller 27. HOW TO ASSIGN GROUP/ FRT Function: It's more convenient to edit logic with "Group". There are four groups in the system: detection group, control output group, supervision group and FRT group. See Appendix table 3 for details. Steps: Press “Menu”...
  • Page 47: How To Get Help

    Operating Manual of FC18 Controller 28. HOW TO GET HELP Function: To show the company name, system edition, product series No, download time of configuration file and modification time. Steps: Press “Menu” to browse the main menu (Fig. 27-1). Main menu displayed. Press “→”...
  • Page 48: How To Operate Interlocking Panel

    Operating Manual of FC18 Controller 29. HOW TO OPERATE INTERLOCKING PANEL Function: The interlocking penal has 8 channels of input/output. Each of them has indicators of trouble, activation and confirmation to indicate its status, as well as activation/deactivation key for manual control. Steps: ¹...
  • Page 49: How To Open/Close Printer

    Operating Manual of FC18 Controller 30. HOW TO OPEN/CLOSE PRINTER Function: When the printer is open, it can print real-time events at any time and print history records if needed (see "History Query"); when it's close, it cannot print anything. Steps to open printer: Press “Menu”...
  • Page 50 Operating Manual of FC18 Controller Operations of printer: There are two indicators and two keys which are combined. Indicator: Green indicator indicates power status of printer; red indicator indicates working status of printer (online/offline). Green Normal power supply indicator No power supply Online Red indicator Offline...
  • Page 51: How To Replace Device

    Operating Manual of FC18 Controller 31. HOW TO REPLACE DEVICE Function: To copy the configuration information to the new device when the old one is replaced. Steps: Press “Menu” to browse the main menu (Fig. 30-1). Main menu displayed. Fig.30-1 Press “→”...
  • Page 52: How To Change Language

    Operating Manual of FC18 Controller 32. HOW TO CHANGE LANGUAGE Function: The system provides four kinds of language: English, Taiwan, Hong Kong, Portuguese. One of them can be selected according to needs. Steps: Press “Menu” to browse the main menu (Fig. 31-1). Main menu displayed.
  • Page 53: How To Query The Information Of Other Events

    Operating Manual of FC18 Controller 33. HOW TO QUERY THE INFORMATION OF OTHER EVENTS Function: Other events include: Test, Walktest, Locate, Unconfigure, Unknown, Inconsistent, Exchage. Through this function, can check the quantity for each event. Step: Press “Menu” to browse the main menu (Fig. 31-1). Main menu displayed.
  • Page 54: How To Extend Printer Port

    Operating Manual of FC18 Controller 34. HOW TO EXTEND PRINTER PORT Function: when the communication port on the main board is occupied by the FMS8000 graphic display device, the debugging port on the CPU board can be configured as the printer port via this operation。 Steps: Press “Menu”...
  • Page 55: How To Synchronize Configuration

    Alarm & active Alarm & active Trouble System Normal and the configuration file of each slave controller is updated accordingly. Supervision System Normal SIEMENS Building SIEMENS Building Steps: Disable SIEMENS Test Press “Menu” to browse the main menu (Fig. 35-1) Walk-Test Main menu displayed.
  • Page 56: How To Collect Configuration And Synchronize

    Brow Oper Conf Tool Help Login Alarm & active Alarm & active Trouble System Normal Steps: Supervision System Normal SIEMENS Building SIEMENS Building Press “Menu” to browse the main menu (Fig. 36-1) Disable SIEMENS Test Main menu displayed. Walk-Test <2008-08-08 08:08:08>...
  • Page 57: How To Check The Summary Of Controller Auto/Manual Status

    Operating Manual of FC18 Controller 37. HOW TO CHECK THE SUMMARY OF CONTROLLER AUTO/MANUAL STATUS Function: The FC18 fire alarm controller can check the summary of auto or manual status for each controller in the network via this operation. Steps: Press “Menu”...
  • Page 58: Chapter 4 Maintenance

    Operating Manual of FC18 Controller CHAPTER 4 MAINTENANCE 1. DAILY EXAMINATION People on duty should examine controllers every day and record status. If there is alarm, trouble or other abnormal status, please follow “Emergency and Trouble Handing”; when controller gets normal again, the event should be recorded. 2.
  • Page 59 Operating Manual of FC18 Controller Failure Status Cause Analysis Recommend Solving Method Configuration file does not consist with actual Change configuration file; equipment; External voltage exceed power requirement; Adjust external voltage range; Power trouble Battery is damaged; Change battery; Power is damaged; Change power supply;...
  • Page 60: Appendix 1 Parameter List

    Operating Manual of FC18 Controller APPENDIX 1 PARAMETER LIST Equipment type Editable item Parameter description System Text System name Station Text Controller name - FC1820 Login time Under 2nd/3rd level, if there is no operation in preset login time, controller - FC1840 will automatically log out to 1 level.
  • Page 61 Operating Manual of FC18 Controller Alarm input Text Device location/function description (interlocking panel and main board input) Output without confirmation Text Device location/function description (FDCIO181) Inversion Option 1: Normal (Active When NO is closed) (default) Option 2: Inverting (Active when NC is open) Signal Shape Option 1: Static (After activating, the output remains permanently active) (default)
  • Page 62 Operating Manual of FC18 Controller Output style Switched voltage control output. (Default) Option 1: Dry contact Option 2: Output with confirmation Text Device location description (interlocking panel and main Supervision time In preset supervision time, if there is no confirmation signal received, board output) system defines it as activation without confirmation.
  • Page 63: Appendix 2 Operable Item List

    Operating Manual of FC18 Controller APPENDIX 2 OPERABLE ITEM LIST Controller: Operational item Controller Auto/Manual Set time System Check FC1820 √ √ √ √ √ √ FC1840 FC186X √ √ √ ] Auto/Manual can only be switched through buttons on controllers. Line: Operational item Line...
  • Page 64 Operating Manual of FC18 Controller Group: Group Operational item Activation/ Disable/ Deactivation Enable Control group √ ------- Detection group ------- ------- Supervision group ------- -------- FRT group ------- √ “Ö“ indicates operational; “----” indicates not operational. Page: 63/70...
  • Page 65: Appendix 3 Devices Grouping Table

    Operating Manual of FC18 Controller APPENDIX 3 DEVICES GROUPING TABLE Detecting Control output Supervision Device type group group group group FDO181 Smoke detector √ √ FDT181 Heat detector √ √ FDM181 Manual Call Point √ √ FDCI181 Input module √ FDCIO181 Input/output module √...
  • Page 66: Appendix 4 Rules For Logic Expression

    Operating Manual of FC18 Controller APPENDIX 4 RULES FOR LOGIC EXPRESSION Logic expression: 01.0001.07+01.0002.07+01.0003.07=01.0004.10 Input Output Group No.: xx.xxxx First two number express controller number. Last four number express group code. ① Status code:xx express the status in the logic ②...
  • Page 67 Operating Manual of FC18 Controller ● “@N”: Union alarm in a group, 2≤N≤ total device amount; Example: 01.0001@2=01.0004; indicates that any 2 devices in group 01.0001 alarm can activate group 01.0004. Remark: when adding /deleting device in a group, the logic expression needs to be verified. ●When a logic expression need to activate more groups (output) simultaneously, use “,”...
  • Page 68: Appendix 5 Input Method

    Operating Manual of FC18 Controller APPENDIX 5 INPUT METHOD Letter/Number input: Press down letter/number key, then input content will switch between number and letter. When switched to needed content, relieve the key to complete the input of needed letter/number. Special character input: Press down number key (1), then input content will switch among '1', '.', '+', '*', '=', ';', '~', '(', ')', '[', ']', '{', '}', '!', ':', ‘space’, '-'.
  • Page 69: Appendix 6 "Sticker Method"Easy For Commissioning

    Operating Manual of FC18 Controller APPENDIX 6 “STICKER METHOD”EASY FOR COMMISSIONING In FC18 system, each field device has a unique ID number. Engineer can tear it down when installing, and fix to the equipment position in engineering drawings, so that after finishing installation of all devices, engineer file configuration can be made. Detailed procedures are as follows: Open the package.
  • Page 70 © Beijing Siemens Cerberus Electronics Ltd., 2014 Issued by Beijing Siemens Cerberus Electronics Ltd. Technical specifications and availability subject to change without notice. No.1, Fengzhi East Road, Xibeiwang Haidian District, 100094 BEIJING, China +86 10 64768806 www.siemens.com/buildingtechnologies Doc. No. A6V10322053_e_en_--...