17. HOW TO SET LOGIN TIME

Function: Under 2/3 level, if there is no operation in preset login time, controller
will automatically log out to 1level. Setting range: 1-60 minutes.
Steps:
1.
Press "Menu" to browse the main menu (Fig. 17-1)
Main menu displayed.
2.
Press "→" to select "Browse" submenu (Fig. 17-2). Select "All" and then
press "OK". Now the tree diagram will be displayed in the window
(Fig.17-3).
3.
Use "↓" / "↑" to select the controller you are looking for.
4.
Press "→" to pop out the shortcut menu (Fig.17-4). Use "↓" to select "Edit
Parameter" and press "OK" to enter the parameter editing interface
(Fig.17-5).
5.
Press "↓" to select "Login Time" window. Press "←" to delete the previous
number and enter the expected one.
6.
After the change, press "Menu" and press "↓" to select "Confirm", then
press "OK" to save the change and quit. A dialog box will pop out to remind
you to save the change (Fig. 22-3). Press "OK" to save the change
permanently or press "C" to save the change temporarily. (The change will
be lost if the system is restarted.)
Select "Cancel" and press"OK" if you don't want to save the change.
Note: The saved changes take effect immediately.
These operations can only be applied to the selected controller.
Operating Manual of FC18 Controller
Fig.17-1
Fig.17-2
Fig.17-3
Fig.17-4
Fig.17-5
Page: 34/63