13. HOW TO ACTIVATE/DEACTIVATE THE CONTROLLER

Function: Through controller, manually activation/deactivation mainboard
output, output module, interlocking panel output and NAC devices etc.
Steps to activation:
1.
Press "Menu" to browse the main menu (Fig. 13-1).
Main menu displayed.
2.
Press "→" to select "Brow" submenu (Fig. 13-2). Press "↓" to select "All",
then press "OK" to display the tree diagram (Fig. 13-3). Search down level
by level through stations, lines and points until you find the equipment you
are looking for.
3.
Press "→" to pop out a shortcut menu (Fig.13-4). Use "↓" to select
"Activate" and press "OK" to activate the selected equipment.
4.
Press "Acknowledge/Silence" to silence the buzzer and to turn off the
flashing "Acknowledge/Silence" indicator.
Steps to deactivate (two ways):
The first way: the same as the first 2 steps to activation. The only difference is
that select "Deactivate" instead of "Activate" in step 3.
The second way: It's easier to find the activated equipment through real-time
activation query (see real-time query). Press "→" to pop out a shortcut
menu (Fig. 13-5) and press "↓" to select "Deactivate", then press "OK"
to deactivate the selected equipment.
Activation indicator turns off when all the activated equipments are
deactivated.
Operating Manual of FC18 Controller
Fig.13-1
Fig.13-2
All
SIEMENS Buidling
Building 1 Controller
Power Monitor Line
Onboard I/O
NAC
Main Board I/O 1
Main Board I/O 2
P2 Line
Fig.13-3
All
SIEMENS Buidling
Property
Building 1 Controller
History
Power Monitor Line
Activate
Activate
Onboard I/O
Disable
NAC
Edit Parameter
Main Board I/O 1
Main Board I/O 2
P2 Line
Fiig.13-4
Fig.13-5