12.1.3 Communication Specifications
Tool port
Item
Interface
Communication mode
Transmission distance
Baud rate
(to be set by system register)
Note3)
Communication method
Synchronous method
Transmission line
Trans-
Computer link
mission
General-purpose
code
serial communication
Data length
Communication
Parity
format
(to be set by
Stop bit
system register)
Start code
Note1)
End code
No. of connected units
Communication functions
Note1) The start code and end code can be used only in the general-purpose serial communication
mode.
Note2) Unit numbers should be registered by the system register.
Note3) The baud rates of 300, 600 and 1200 bps can be specified by the SYS instruction only.
Note4) Although it has adequate tolerance to noise, it is recommendable to make the user program to
execute retransmission. (in order to improve reliability of the communication in case of
communication errors occurred by excessive noises or when a receiver equipment cannot receive
temporarily.)
12-6
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
RS232C
1:1 communication
15 m
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
Half-duplex communication
Start stop synchronous system
Multicore shielded line
ASCII
ASCII, Binary
7 bits/8 bits
None/Even/Odd
1 bit/2 bits
STX/No STX
CR/CR+LF/None/ETX
Note2)
2 units
Computer link (slave)
Modem initialization
General-purpose communication (only in RUN mode)
Specifications