Appendix C S5 Adapter/Cp 525 Error Codes; S5 Unilink Adapter Primitive Exceptions; Primitive Exceptions; Primitive Exception Error Byte - Siemens SIMATIC TI505 Installation And Operation Manual

S5 unlink adapter
Hide thumbs Also See for SIMATIC TI505:
Table of Contents

Advertisement

C.1

S5 UniLink Adapter Primitive Exceptions

Primitive
Exceptions
C-2
S5 Adapter/CP 525 Error Codes
During operation, two possible error codes could be returned by the
S5 UniLink Adapter: primitive exceptions, and CP 525 errors.
The error byte of a primitive exception contains one of the following.
Request:
None
Response: LLLL 00 PP DDDD
Table C-1 Primitive Exception Error Byte
Symbol
Value
PP
Request primitive code that contains the exception.
DDDD
0000
The primitive code is not implemented in the S5 PIM.
0001
There is no corresponding S5 memory type that maps to the
TT type supplied.
0002
Data element location (specified by TT) is out of range (See
Note).
0003
Primitive has excess data unit bytes.
0004
Primitive has insufficient data unit bytes.
0005
The number of information bytes received does not match the
number of bytes specified in the field length.
000A
The attached CP 525 module fails to respond.
000E
Primitive not valid for the specified data type (TT).
0010
The number of locations requested exceeds the maximum
allowed (See Note).
0011
The number assigned to a data acquisition block or record is
not within the supported block or record range.
0012
The block or record number requested has not been defined.
0013
The number of data bytes in the requested blocks or records
exceeds the maximum number of bytes allowed by the
primitive.
0017
The attached device did not respond properly.
0019
The resulting data element location formed by the starting
address, plus the number of data elements to access, is out of
range specified by TT.
001A
Communications has not been established with the attached
device.
001D
The number of locations to access is zero (NNNN = 0).
0024
An illegal IEEE floating-point value (an IEEE NaN,
Not-a-Number) exists in a primitive write request.
Definition
S5 UniLink Adapter Installation and Operation

Advertisement

Table of Contents
loading

Table of Contents