TH 192 Adapter Kits
Description
Installation
Instructions
General Procedure
Controls
The TH 192 Adapter Kits are designed to convert most existing pneumatic room
thermostats to Powers TH 192 or 194 Series or
Thermostats.
The Universal Adapter Kit contains the parts needed for all conversions. Adapter Kits
"A" and "B" do not contain all the parts that are included in the Universal Adapter Kit.
Therefore, kits "A" and "B" are suitable only for specific conversions.
See Table 1 to select the required kit and also to locate the page where the parts used
in a specific conversion are indicated.
The following general procedure applies for all thermostat installations. Notice that
some installations will require the use of the adapter frame to cover up paint lines,
broken walls, spots, etc. For installations not covered in this bulletin, remove the old
terminal and connect directly to the tubing. See Figures 2, 3 and 4.
1. Remove old thermostat from the wall.
2. Remove terminal head and gasket from fitting.
3. Clean fitting surface if required.
4. See Table 1 and locate page on conversion being made.
5. Identify correct mounting parts and necessary instructions.
6. Proceed with the connections required. Secure all connections and install plug-in
adapters to the 5/32-inch (4 mm) plastic tube. Use blue adapter for the air supply
line.
NOTE:
Either the polyethylene (hard) or polyurethane (soft) tubing is
recommended on each specific conversion. This selection is based on
the most compatible application.
Technical Bulletin
Document No. 155-231P25
Rev. 2, December, 2001
Free Energy Band
Siemens Building Technologies, Inc.
TB-214
TH 193 HC

Advertisement

loading

Summary of Contents for Siemens Powers TH 192

  • Page 1 The TH 192 Adapter Kits are designed to convert most existing pneumatic room ™ Free Energy Band thermostats to Powers TH 192 or 194 Series or TH 193 HC Thermostats. The Universal Adapter Kit contains the parts needed for all conversions. Adapter Kits "A"...
  • Page 2 If this happens, bend the latch arms back to their operating position before mounting the thermostat. 192-300 Universal Kit 192-483 Adapter Kit "A" 192-484 Adapter Kit "B" Figure 1. Adapter Kits. Page 2 Siemens Building Technologies, Inc.
  • Page 3 On Draeger Thermostats, the air lines are normally 5/32-inch O.D. plastic tubing and the multi-slotted plate can be mounted using slots 1 and 14. On UPC Thermostats, the air lines are normally 1/4-inch O.D. plastic tubing and the multi-slotted plate can be mounted using slots 12 and 13. Siemens Building Technologies, Inc. Page 3...
  • Page 4 Technical Bulletin Powers Controls TH 192 Adapter Kits Document Number 155-231P25 Rev. 2, December, 2001 Figure 2. Thermostat Mounting with Universal Kit – Option 1. Figure 3. Thermostat Mounting with Universal Kit – Option 2. Page 4 Siemens Building Technologies, Inc.
  • Page 5 *See Field Purchasing Guide for Energygard ordering information. A. Cover C. (4) Anchor B. Frame D. (4) Expander Nail Figure 5. Universal Kit with Thermostat and Energygard* Model P Guard. Page 5 Siemens Building Technologies, Inc.
  • Page 6 *P. (2) Plug-in Adapter (2) No. 6-32 × 1-inch Long Binder Head Screw *Items not shown. See Figure 2 for proper installation. Figure 7. Powers Controls TH 180,182,192 Conversion From Horizontal To Vertical Installation. Page 6 Siemens Building Technologies, Inc.
  • Page 7 *Items not shown. See Figure 2 for proper installation. *Items not shown. See Figure 2 for proper installation. Figure 9. Honeywell HO, HP, TO, TP, TRO 900 Figure 10. Honeywell TP 410, 910 To 924, 933 Flush Box. Flush Banjo. Page 7 Siemens Building Technologies, Inc.
  • Page 8 *P. (2) Plug-in Adapter *Items not shown. See Figure 2 for proper installation. *Items not shown. See Figure 2 for proper installation. Figure 13. Honeywell TP 901A, B Plaster Back. Figure 14. Honeywell TP901C Mullion or Partition. Page 8 Siemens Building Technologies, Inc.
  • Page 9 *Items not shown. See Figure 2 for proper installation. *Items not shown. See Figure 2 for proper installation. Figure 17. Honeywell TP 970-974 Deep Wall Box. Figure 18. Johnson H & T 4000, 5000 Surface Fitting. Page 9 Siemens Building Technologies, Inc.
  • Page 10 (2) Tubing Adapter (5/32-inch × 5/32-inch or 1/4-inch × 5/32-inch) *P. (2) Plug-in Adapter *Items not shown. See Figure 2 for proper installation. Figure 21. Swan, Bishop & Babcock Flush Fitting. Figure 22. Robertshaw T18, T19, 32 Flush Box. Page 10 Siemens Building Technologies, Inc.
  • Page 11 (2) Tubing Adapter (1/4-inch × 5/32- inch or 5/32-inch × 5/32-inch) *P. Plug-in Adapter *Items not shown. See Figure 2 for proper installation. Figure 25. Robertshaw H 10, 50, 52, T15, 16, 21, 25, 26, 30, 31, 51, 52 Drywall, Mortar Joint or Surface. Page 11 Siemens Building Technologies, Inc.
  • Page 12 Powers and are trademarks of Siemens Building Technologies, Inc. Other product or company names mentioned herein may be the trademarks of their respective owners. © 2001 Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. Your feedback is important to us. If you have Document No.