Write and Gather
Block
S5 UniLink Adapter Installation and Operation
The Write and Gather Block primitive specifies which blocks (as defined
with Define Block primitive 50) will be read. It also allows a user to replace
any contiguous data element locations. The blocks are specified through a
32-bit mask (EEEEEEEE).
The Write occurs first, followed by the Gather. Refer to Gather Block for the
bit masking information and other related items concerning the operation of
this primitive.
Request:
LLLL 52 EEEEEEEE TT AAAA DD ... DD
Symbol
EEEEEEEE
Bit mask (See above).
TT
Data element type.
AAAA
Data element location.
DD
Data.
Response: LLLL 52 HH EEEEEEEE DD ... DD
Symbol
HH
Operational status (see Status).
EEEEEEEE
Bit mask (See above).
DD
Data.
Definition
Definition
TIWAY I Primitives Supported by S5 PIM
B-9