Output Bytes - Cp 525 'A' Type; Description; Address Mapping; Value Conversion - Siemens SIMATIC TI505 Installation And Operation Manual

S5 unlink adapter
Hide thumbs Also See for SIMATIC TI505:
Table of Contents

Advertisement

A.6
Output Bytes — CP 525 'A' Type

Description

Address Mapping

Value Conversion

Reading and
Writing
S5 UniLink Adapter Installation and Operation
The S5 Output Bytes memory, as accessed through a CP module, refers to
memory that is organized in 128 contiguous bytes of memory. Because the
output image memory area (A memory) is accessible only if a corresponding
I/O module is in use, the S5 PIM assumes no knowledge of the accessible
memory area of the process output image. The TT types that map to this
type of S5 memory are Packed Output Discretes (TT Type 07) and Unpacked
Output Discretes (TT Type 04).
NOTE: If a TIWAY request is out of range, the exception returned will be of
the form 80DD.
TI500/TI505 Output Memory Address
Address = YYYY (hex)
When converting the value for Packed Discretes, the most significant bit
(MSB) of the TI500/TI505 value corresponds to the least significant bit
(LSB) of the S5. When converting the value for the Unpacked Discretes, the
byte on/off state of the TI500/TI505 corresponds to the bit specified in the
S5.
Contents of TI500/TI505 Packed Outputs
0
1
2
3
4
First discrete bit accessed
Contents of TI500/TI505 Unpacked Outputs
00's
Reading the CP 525 A memory with the TT types 04 and 07 is supported.
Writing to the CP 525 A memory with TT types 04 and 07 is not supported
due to the functionality of the CP module itself.
Byte Address:
Quotient of (YYYY / 8)
Bit Address:
Remainder of (YYYY / 8)
Contents of S5 Output Bytes
5
6
7
0
Only discrete bit accessed
Simatic S5 Memory Mapping
S5 Input Bytes Memory
7 6 5 4
3 2 1 0
7
6
5
4
3
2
First discrete bit accessed
1
0
A-7