Overview

Exception

B-2
TIWAY I Primitives Supported by S5 PIM
TIWAY I Primitives provide a uniform command level access to industrial
devices through the TIWAY I Industrial Local Area Network. This section
describes the set of primitives supported by the S5 UniLink Adapter*.
The S5 PIM supports the following exception field values.
Request:
None
Response: LLLL 00 PP DDDD
Symbol
Value
PP
Request primitive code that contains the exception.
DDDD
0000
The primitive code is not implemented in the S5 PIM.
0001
There is no corresponding S5 memory type that maps to the
TT type supplied.
0002
Data element location (specified by TT) is out of range (see
Note).
0003
Primitive has excess data unit bytes.
0004
Primitive has insufficient data unit bytes.
0005
The number of information bytes received does not match the
number of bytes specified in the field length.
000A
The attached CP 525 module fails to respond.
000E
Primitive not valid for the specified data type (TT).
0010
The number of locations requested exceeds the maximum
allowed (see Note).
0011
The number assigned to a data acquisition block or record is
not within the supported block or record range.
0012
The block or record number requested has not been defined.
0013
The number of data bytes in the requested blocks or records
exceeds maximum number of bytes allowed by the primitive.
0017
The attached device did not respond properly.
0019
The resulting data element location formed by the starting
address, plus the number of data elements to access, is out of
range specified by TT.
001A
Communications has not been established with the attached
device.
001D
The number of locations to access is zero (NNNN = 0).
0024
An illegal IEEE floating-point value (an IEEE NaN,
Not-a-Number) exists in a primitive write request.
80DD
An exception was generated by the CP 525 module, and its
byte value is contained in the DD field.
*This material assumes you have prior knowledge of TIWAY primitives. Refer to the TIWAY
Primitive Compatibility Specification for specific details.
Definition