Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A.
Installation Instructions
SAFETY INSTRUCTIONS
NOTE: This instruction outlines the recommended
installation procedure.
1. Circuit Breaker Preparation
The circuit breaker should be in the OFF/"O"
position before installing the plug-in-tulip adapter
kit. Turn off and lock out all power supplying this
device before installing. Verify that NO voltage
is present before proceeding with task.
Dimensions
Inches
[Millimeters]
Hazardous voltage.
Will cause death or
serious injury.
Turn OFF and lock out all
power supplying this
device before installing
or servicing accessory.
Cat. No. TCM2, TCM3 Plug-In Adapters
Item:
SIEMENS
For use with:
cuit Breakers Types: MD6, MM6, MMK, MFC, MFF,
HMD6, CMD6, SMD6,SHMD6, SCMD6, MD6ETI,
CMD6ETI, and Molded Case Switch Type MXD6 in
conjunction with plug-in-mounting assemblies Cat.
No.'s PC5662, PC5663 and PM5663.
1
2
Page
of
410904A01
Pc. No.
Remove Pressure Wire Connectors From
Breaker If Present
2. Loosen four breaker terminal shields screws (6)
and remove both line and load side terminal
shields (7).
3. Place tulip clip assembly (8) on back of breaker
in recess provided in base molding. Secure in
place with 5/16-18 hex head bolts (11) furnished.
Tighten these bolts to 72 In.-Lbs. (6 Ft.-Lbs.)
[8.13 N/m] to assure a good electrical connec-
tion. Repeat this procedure for the remaining
tulip clip assemblies.
4. INSERT END SHIELDS (12) INTO SLOTS PRO-
VIDED AT LINE AND LOAD END OF
BREAKER.
5. Affix label (13) to front of circuit breaker as shown
in Fig. 4.
.25
[6.35]
Fig. 4
®
MD, MM & MF Frame Cir-