TEST
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
Induced (Conducted) RFI
IEC 61000-4-8
IEC 61000-4-29
Voltage Dips & Interrupts
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
Mains Frequency Voltage
IEC 61000-4-17
Ripple on D.C. Power Supply
IEC 60255-5
IEC 60255-5
Test
IEEE C37.90.3
IEEE C37.90.2
IEEE C37.90.1
IEEE C37.90.1
IEEE C37.90
IEEE C37.90
MIL-STD
MIL-STD-901D *
MIL-STD-167-1 *
MIL-STD-461E *
MIL-STD-1399 *
MIL-STD-810F *
MIL-STD-810 *
MIL-STD-810 *
Notes:
1. Only applicable to functional earth connections separated from the safety earth connection.
2. Class 2 refers to "Measuring relays and protection equipment for which a very high security margin is required or where
the vibration levels are very high, ( e.g. shipboard application and for severe transportation conditions")
www.RuggedCom.com

EMI and Environmental Type Tests

IEC 61850-3 EMI TYPE TESTS
Description
Enclosure Contact
ESD
Enclosure Air
Radiated RFI
Enclosure ports
D.C. Power ports
Burst (Fast Transient)
A.C. Power ports
Earth ground ports 3
Surge
D.C. Power ports
A.C. Power ports
D.C Power ports
A.C. Power ports
Earth ground ports 3
Magnetic Field
Enclosure ports
D.C. Power ports
A.C. Power ports
Damped Oscillatory
D.C. Power ports
A.C. Power ports
D.C. Power ports
D.C. Power ports
Dielectric Strength
D.C. Power ports
A.C. Power ports
H.V. Impulse
D.C. Power ports
A.C. Power ports
IEEE 1613 (C37.90.x) EMI IMMUNITY TYPE TESTS
Description
Enclosure Contact
ESD
Enclosure Air
Radiated RFI
Enclosure ports
D.C. Power ports
Fast Transient
A.C. Power ports
Earth ground ports3
D.C. Power ports
Oscillatory
A.C. Power ports
H.V. Impulse
D.C. Power ports
A.C. Power ports
Dielectric Strength
D.C. Power ports
A.C. Power ports
MILITARY STANDARD TESTS
Description
Shock (Hard-Mounted)
Vibration
Electromagnetic Interference
Magnetic Field - DC Magnetic Exposure
Temperature - Low/High Temperature
Temperature - Non-operating Thermal Shock
Humidity
MIL-STD 9-Port Managed Gigabit Ethernet Switch
+/- 8kV
+/- 15kV
20 V/m
Signal ports
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
Signal ports
+/- 4kV line-to-earth, +/- 2kV line-to-line
+/- 2kV line-to-earth, +/- 1kV line-to-line
+/- 4kV line-to-earth, +/- 2kV line-to-line
Signal ports
10V
10V
10V
10V
40 A/m continuous, 1000 A/m for 1 s
30% for 0.1s, 60% for 0.1s, 100% for 0.05s
30% for 1 period, 60% for 50 periods
100% for 5 periods, 100% for 50 periods 2
Signal ports
2.5kV common, 1kV diff. mode@1MHz
2.5kV common, 1kV diff. mode@1MHz
2.5kV common, 1kV diff. mode@1MHz
Signal ports
30V Continuous, 300V for 1s
30V Continuous, 300V for 1s
10%
Signal ports
2kVac (Fail-Safe Relay output)
2kVac
2kVac
Signal ports
5kV (Fail-Safe Relay output)
5kV
5kV
+/- 8kV
+/- 15kV
35 V/m
Signal ports
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
Signal ports
2.5kV common mode @1MHz
2.5kV common, 1kV diff. mode@1MHz
2.5kV common, 1kV diff. mode@1MHz
Signal ports
5kV (Fail-Safe Relay output)
5kV
5kV
Signal ports
2kVac
2kVac
2kVac
Grade A, Equipment Class I, Shock Type A Equipment
Type I (Upper Frequency of 33 Hz)
CE101, CE102, CS101, CS114, CS115, CS116, RE101, RE102,
RS101, RS103
Section 070, Part 1
Method 501
Method 503
Method 507, Procedure IV
* Testing complete, pending final documentation (contact RuggedCom for complete details)
®
RuggedSwitch
Test Levels
Severity Levels
Test Levels
Severity Levels
Details
RuggedSwitch
®
M2200
M2200
4
4
x
x
4
4
4
4
3
4
3
3
3
3
N/A
N/A
N/A
N/A
3
3
3
4
4
3
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A