Preparation Of The Fireplace Opening; Fireplace Opening Size; Shelf Position; Fireguard Requirements - Vision V1/200/A Installation & User's Instructions

Inset coal effect gas convector fire
Table of Contents

Advertisement

PREPARATION OF THE FIREPLACE OPENING

The appliance must be installed mounted on a non-combustible hearth. It must not be installed
directly on any combustible material. The hearth must be at least 12mm thick with a periphery
thickness of at least 50mm. It should be at least 700mm wide and project at least 300mm for-
wards from the fire opening.
The appliance must be fitted into a non combustible opening.
The area around the fire opening (where the appliance side and top flanges meet it) should be
reasonably flat to ensure a good seal. If necessary, take appropriate measures to ensure this.
The floor within the fireplace opening should be reasonably flat to ensure a good seal can be
made at the bottom of the appliance.
Any underfloor air supply to the fire opening must be sealed off completely.
The appliance can be fitted with a non combustible fireplace surround or a proprietary fireplace
surround with a temperature rating of at least 150°C.

FIREPLACE OPENING SIZE

When preparing the opening, please observe the following dimensions are met:
MINIMUM OPENING SIZE
MAXIMUM OPENING SIZE

SHELF POSITION

The appliance can be installed below a combustible shelf as long as there is a minimum distance
of 750mm from the top of the hearth and the shelf does not project more than 150mm. If the shelf
projects more than 150mm then the distance between the top of the hearth and the shelf needs to
increase by 15mm for every additional 25mm of projection beyond 150mm.

FIREGUARD REQUIREMENTS

A fireguard complying with BS 8423 should be fitted for the protection of children, the elderly,
the infirm and pets.
INSTALLATION REQUIREMENTS
WIDTH
405mm
457mm
HEIGHT
555mm
575mm
5
DEPTH
200mm
-