MANUAL CLOSE BLOCKING
8–42
RAISE NEUTRAL TOC 1 (2, 3, 4) PKP
Range: 1 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the NEUTRAL TOC 1/2 protection element
by raising the Pickup level.
RAISE GROUND TOC 1 (2, 3, 4) PKP
Range: 1 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the GROUND TOC 1 protection element by
raising the Pickup level.
RAISE SENS GND TOC 1/2 PKP
Range: 1 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the SENSITIVE GROUND TOC 1 protection
element by raising the Pickup level.
RAISE NEG SEQ TOC 1/2 PKP
Range: 1 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the NEGATIVE SEQUENCE TOC 1
protection element by raising the Pickup level.
SELECT SETPOINT GROUP
Range: Active, Group 1,2,3,4,5,6
Default: Active
The setpoint determines the setpoint group that is used after the Manual Close Blocking
condition is detected.
OUTPUT RELAY X
For details see
Common
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
Setpoints.
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL