CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
NOTE:
NOTE
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
ENABLE PASSWORD COMPLEXITY
Range: Disabled, Enabled
Default: Disabled
This setting is available to provide the option of selecting between simple passwords and
complex ones. The following conditions apply:
The setting is only available to Administrator
By default password complexity is disabled
When password complexity is enabled, it follows the rules defined in the
Password Complexity section.
SYSLOG IP ADDRESS
Range: 0.0.0.0 to 223.255.255.254
Default: 0.0.0.0
This is the IP address of the target Syslog server all security events are transmitted to.
SYSLOG PORT NUMBER
Range: 1 to 65535
Default: 514
This sets the UDP port number of the target Syslog server all security events are
transmitted to.
SETPOINT ACCESS
Range: Off, On, Digital Input
Default: Off
The setting is only available to Administrator.
The setpoint access setting may be assigned to a digital input.
When the digital input is activated, the user gets Administrator access to the front
panel.
FACTORY SERVICE MODE
Range: Disabled, Enabled
Default: Disabled
When the feature is enabled, the Factory role is accessible and the device may go
into factory service mode.
The setting may be changed only by an Administrator.
The default value is Disabled.
The factory role password may not be changed.
REQUIRE PW FOR RESET KEY
Range: Disabled, Enabled
Default: Disabled
If this setting is enabled and an alarm or trip occurs on the relay, the Reset button is not
available to the Operator. Only the Administrator can reset the relay with their password.
REQUIRE PW FOR D/T CHANGE
Range: Disabled, Enabled
Default: Disabled
The date/time can be set by any role, if this setting is disabled. If this setting is enabled
the date/time can only be set by the Administrator.
CHANGE PASSWORDS SETTINGS
The two menu items: Change Administrator Password, and Change Operator
Password are available only to Administrator, which is the only role that has
permissions to change passwords for itself and the other local roles.