Transient Records; Data Logger; Fault Reports - GE 850 Instruction Manual

Feeder protection system
Hide thumbs Also See for 850:
Table of Contents

Advertisement

TRANSIENT RECORDS

Transient Records

Data Logger

Fault Reports

12–2
Path:
Records > Transients > Transient Records
Select the record from which you would like to read the values then click the "Launch
Viewer" button to view the waveform.
The 850 Data Logger record can be retrieved and seen from this window. It displays the
oldest and newest timestamps, and the total number of samples captured for all channels
programmed in Setpoints > Device > Data Logger menu.
Path:
Records > Data Logger
The latest fault reports can be displayed.
Path:
Records > Fault Reports
NUMBER OF REPORTS
This value shows the number of reports since the last clear.
LAST TRIP DATE/TIME
Range: MM/DD/YY/ HH:MM:SS
This value is the date and time on which the last report was generated.
LAST CLEAR DATE/TIME
Range: MM/DD/YY/ HH:MM:SS
This value is the date and time on which the record was cleared.
TYPE OF FAULT
Range: N/A, AG, BG, CG, AB, BC, CA, ABG, BCG, CAG, ABC
Default: N/A
This record displays the type of fault.
DISTANCE TO FAULT
Range: 0.00 to 99.99 km/Mile in steps of 0.01 km/Mile
Default: 0.00 km/Mile
This record displays the distance to fault, in kilometers or miles as selected by the UNITS
OF LENGTH setpoint.
FAULT REPORT X TIME
Range: MM/DD/YY/ HH:MM:SS
This value is the date and time on which the specified fault report was generated.