GE 850 Instruction Manual page 113

Feeder protection system
Hide thumbs Also See for 850:
Table of Contents

Advertisement

CHAPTER 3: INTERFACES
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
Table 3-8: Minor Self-test Errors
Self-test Error
Description of Problem How Often the Test is
1
Message
Order Code Error
Hardware doesn't
match order code
CPU S/N Invalid
CPU card doesn't have
valid data to match the
order code.
Slot"$" IO S/N
IO card located in slot $
2
Invalid
doesn't have valid data
to match the order
code.
Comms S/N Invalid Comms card doesn't
have valid data to
match the order code.
CPanel S/N Invalid Control Panel doesn't
have valid data to
match the order code.
PSU S/N Invalid
Power Supply Unit
doesn't have valid data
to match the order
code.
RTC Error
The CPU cannot read
the time from the real
time clock
Product Serial
The product serial
Invalid
number doesn't match
the product type
Comm Alert #1
Communication error
between CPU and
Comm Alert #2
Comms board
Comm Alert #3
FLASH Error
The permanent storage
memory has been
corrupted
SPI Error
Communication error
between CPU and LEDs,
Keypad or peripheral
memory devices
Invalid MAC
MAC address is not in
Address
the product range
Calibration Error
Unit has default
calibration values
WiFi Default
SSID and Passphrase is
Settings
the factory default
Link Error Primary
Port 1 or Port 4
3
(depending on order
code) is not connected
Link Error
Port 5 is not connected Every 1 second
Secondary
FRONT CONTROL PANEL INTERFACE
What to do
Performed
Every 1 second
If alert doesn't self-reset then
contact factory. Otherwise
monitor re-occurrences as
Every 1 second
errors are detected and self-
reset
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Every 1 second
Boot-up and Every 1
second
Every 1 second
Set SSID and Passphrase
Every 1 second
Ensure Ethernet cable is
connected, check cable
functionality (i.e. physical
damage or perform
continuity test), and ensure
master or peer device is
functioning. If none of these
apply, contact the factory.
Ensure Ethernet cable is
connected, check cable
functionality (i.e. physical
damage or perform
continuity test), and ensure
master or peer device is
functioning. If none of these
apply, contact the factory.
3–19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents