Power Cable Protection; Frame Size R5 - ABB ACS800-U4 Hardware Manual

Drive modules
Hide thumbs Also See for ACS800-U4:
Table of Contents

Advertisement

Frame size R6: Cable terminal installation [95 to 185 mm
cables]
U1
U1
R-
W1
V1
U1
Input power cable

Power cable protection

Frame size R5

Cover the power cable terminals as follows:
1. Cut holes for the installed cables into the clear plastic shroud.
2. Press the shroud onto the terminals.
1
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
UDC+
U2
R+ UDC-
V2
PE
Motor cable
2
2
(3/0 to 2×4/0 AWG)
W2
b
a
a. Connect the cable to the terminal.
b. Connect the terminal to the drive.
WARNING! If the wire size is less than
2
95 mm
(3/0 AWG), a cable lug must
be used. A cable of wire size less than
2
95 mm
(3/0 AWG) connected to this
terminal will loosen and may damage
the drive.
65