Cable entries
Brake resistor, input and motor cable (per phase) terminal sizes and tightening
torques are given below
Frame
size
Maximum wire size
R2
R3
R4
R5
R6
* 6 AWG rigid solid cable, 8 AWG flexible stranded cable
** with cable lugs 6...2/0 AWG, tightening torque 14.8...29.5 lbf ft. Cable lugs are not included in the
delivery. See page 64.
Dimensions, weights and noise
Frame size
Height
in.
R2
14.57
R3
16.54
R4
19.29
R5
23.70
R6
27.56
* Depth depends on the options included in the drive.
Input power connection
Voltage (U
)
1
Rated conditional short-
circuit current (IEC 60439-1)
Short-circuit current
protection (UL 508 C
CSA C22.2 No. 14-05)
Frequency
Imbalance
Fundamental power factor
(cos phi
)
1
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
.
U1, V1, W1, U2, V2, W2, R+, R
Tightening torque
AWG
up to 6 *
up to 6 *
up to 4
10...2/0
3/0...2×4/0 **
14.8...29.5
Width
in.
6.5
6.81
9.45
10.43
11.81
208/220/230/240 V AC 3-phase ±10% for 230 V AC units
380/400/415 V AC 3-phase ±10% for 400 V AC units
380/400/415/440/460/480/500 V AC 3-phase ±10% for 500 V AC units
525/550/575/600/660/690 V AC 3-phase ±10% for 690 V AC units
65 kA when protected by fuses given in the
US and Canada: The drive is suitable for use on a circuit capable of delivering not more
than 100 kA rms symmetrical amperes at the drive nominal voltage when protected by
fuses given in the
NEMA data
48 to 63 Hz, maximum rate of change 17%/s
Max. ±3% of nominal phase to phase input voltage
0.98 (at nominal load)
-
Maximum wire size
lbf ft
0.9...1.1
0.9...1.1
up to 8
1.5...3.0
up to 5
11.1
10...2/0
Depth*
in.
7.6...8.9
9.11...10.43
9.93...10.69
10.85...11.11
15.71
IEC data
fuse table.
Earthing PE
Tightening torque
AWG
up to 8
4/0
Weight
lb
18
29
53
71
141
fuse tables.
Technical data
107
lbf ft
1.1
1.1
2.2
11.1
5.9
Noise
dB
62
62
62
65
65