Cable entries
Mains, motor and brake resistor cable terminal sizes (per phase), maximum
accepted cable and tightening torques are given below.
Frame
U1, V1, W1, U2, V2, W2, UDC+/R+, UDC-, R-
size
Number of holes per
phase
R7
3
R8
3
Dimensions, weights and noise
Frame size
H
mm
R7
1121
R8
1564
H
height
W1 width of the basic unit with PE terminal (bookshelf)
W2 width with the cable connection terminal plates on the left side only (bookshelf)
(R7: width with the cable connection terminal plates on both sides is 579 mm)
(R8: width with the cable connection terminal plates on both sides is 776 mm)
D
depth without fastening brackets
(R7 bookshelf: depth with fastening brackets is 516 mm)
(R8 bookshelf: depth with fastening brackets is 571 mm)
W3 width of the basic unit with PE terminal/busbar (flat)
W4 width with the cable connection terminal plates (flat)
Frame size
R7
H
height without top and bottom exit busbar shrouds
W
width
D
depth
*
weight without top entry and bottom exit shrouds
Max. cable
2
mm
1×240 or
2×185
3×240
Busbars on the long side
(bookshelf)
W1
W2
mm
mm
334
427
415
562
IP 00, with bottom exit
H
mm
1126
Screw
Tightening
torque
Nm
M12
50...75
M12
50...75
IP 00
Busbars on the short side (flat)
D
H
W3
mm
mm
mm
473
1181
525
568
1596
607
Weight *
W
D
mm
mm
kg
264
471
91
Earthing PE
Screw
M10
M10
Weight
W4
D
mm
mm
kg
631
259
100
779
403
200
Technical data
93
Tightening
torque
Nm
30...44
30...44
Noise
dB
71
72