Cable Types; Cable Entries; Dimensions, Weights And Noise - ABB ACS800 Series Hardware Manual

Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

Cable types

The table below gives copper and aluminium cable types for different load currents.
Cable sizing is based on max. 9 cables laid on a cable ladder side by side, ambient
temperature 30 °C, PVC insulation, surface temperature 70 °C (158 °F)
(EN 60204-1 and IEC 60364-5-2/2001). For other conditions, size the cables
according to local safety regulations, appropriate input voltage and the load current
of the drive.
Copper cables with concentric
copper shield
Max. load
current
A
34
47
62
79
98
119
153
186
215
249
284

Cable entries

Mains, DC link and motor cable terminal sizes (per phase), accepted cable
diameters and tightening torques are given below
Frame size
Wire size
R5
6...70
R6
95...185 *
* with cable lugs 16...70 mm

Dimensions, weights and noise

Frame size
Drive
R5
R6
Package
R5
R6
Aluminium cables with concentric
copper shield
Cable type
Max. load
current
2
mm
A
3x6
61
3x10
75
3x16
91
3x25
117
3x35
143
3x50
165
3x70
191
3x95
218
3x120
3x150
3x185
U1, V1, W1, U2, V2, W2, UDC+,UDC
Max. cable Ø
IP21
2
mm
mm
35
53
2
, tightening torque 20...40 N
Height
Width
mm
mm
816
265
970
300
1085
400
1145
400
Cable type
2
mm
3x25
3x35
3x50
3x70
3x95
3x120
3x150
3x185
00096931
.
-
Tightening
torque
·
N
m
10
20...40
·
m
IP21
Depth
Weight
mm
390
439
549
585
119
Earthing PE
Wire size
Tightening
torque
2
·
mm
N
m
6...35
15
16...95
8
Noise
kg
dB
65
70
100
73
5
4
Technical data

Hide quick links:

Advertisement

Table of Contents
loading