No.
F6-30
Node Address
<4> <5>
F6-31
Clear Mode Selection
F6-32
PROFIBUS Map Selection
<5>
<1> To start and stop the drive through the PROFIBUS-DP network, set b1-02 to "3". To control the frequency
reference of the drive via the PROFIBUS-DP network, set b1-01 to "3".
<2> If F6-03 is set to 3, then the drive will continue to operate when an EF0 fault is detected. Take proper safety
measures, such as installing an emergency stop switch.
<3> Software versions 1012 and later have F6-07 and F6-08 both set to 1.
<4> All node addresses must be unique. Node addresses 0, 1, and 2 are typically reserved for control, maintenance, and
diagnostic equipment. The ERR light will illuminate when 0 or greater than 125 is entered.
<5> Power must be cycled in order for any setting changes to take affect.
<6> The V1000 and T1000V drives localized for Europe do not have the terminal S7 (Multi-function digital input
command 7).
YASKAWA ELECTRIC TOBP C730600 23C 1000-Series Option SI-P3/V, SI-P3/T Installation Manual
6 PROFIBUS-DP Option Drive Parameters
Name
Select the node address of a PROFIBUS-DP Option.
Selects the action to take when a "Clear Mode"
command is received
0: Resets back to 0
1: Maintains the previous value
0: PPO Type
1: Conventional
Description
Values
Default: 0
Min: 0
Max: 125
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
27