Sensor Identification And Selection; Figure 5-9 Pipe Surface Preparation - Siemens FUS1010 Operating Instructions Manual

Sitrans standard liquid ultrasonic flow meter
Hide thumbs Also See for FUS1010:
Table of Contents

Advertisement

3. After receiving the spacing dimensions from the Installation Menu, prepare the pipe
4. Clean an area 13 mm (1/2-inch) on either side of the sensors.
5. Clean an additional 13 mm (1/2-inch) along the length of the sensors.
5.5.2

Sensor Identification and Selection

Sensor identification
The sensor part number located on the front face provides a detailed identification. For
example, the Part Number: 1011HNS-D1T1-S2 means:
FUS1010 IP65 NEMA 4X & IP66 NEMA 7
Operating Instructions, 01/2013, A5E02951520-AC
surface. De-grease the surface, if necessary, and remove any grit, corrosion, rust, loose
paint, etc. Use abrasive material provided to provide a clean contact surface for the
sensors.
Note
Please note that the instructions show vertical mounting for clarity purposes only. Do not
install sensors on the top of a pipe.
Pipe
Cleaned Areas
Figure 5-9
Pipe Surface Preparation
Model
Hi Precision
NEMA w/F-Conn
Pipe Material
Size
Temperature
Agency Approved
Connecting
5.5 Sensor Installation